Aqua ServicesAqua Services
Gas Chlorinators
Line
Solenoid Driven Metering Pumps
Line
Motor Driven Dosing Pumps
Line
Vacuum Controllers
Line
Chlorine Containers
Line
Chlorine Gas Cylinders
Line
Air Breathing Apparatus
Line

Water Treatment Plant Components

Our company manufactures and supplies an entire range of water treatment plant component like water chlorination systems, direct cylinder mounted gas chlorination systems, motor driven dosing pumps, solenoid driven metering pumps (Exclusive for Accurate Dosing Needs), hydraulic pumps and gaseous exhaust under the brand name of AQUA.

We offer customized solutions for our products as per the specified requirements place by our esteemed clients.





Gas Chlorinators

Normally filtered water appears perfectly clear but is mostly contaminated by Bacteria, Yeast, Virus, Mold, Spores and other germs which are dangerous to human Life.

To kill such germs before allowing water for human consumption, there are several process for disinfecting water.

The use of gas chlorinators for sterilizing water practiced throughout of the world. Chlorination is the most effective and economical way of disinfecting water which makes potable water absolutely safe from water born diseases.

The technique involves mixing chlorine gas and water to form hypochondrias acid. 

Formula :

  • CL2 H2O = HOCL HCL

This kills the harmful bacteria and viruses. Usually, 1 Ltr. of water is required for every 0.5 grams of chlorine Gas for making solution. (10M3 water required for 0.005 mg og chlorine gas to get 0.5 ppm cl2 om water.

Aqua Gas Chlorinators :

It is simple in design and handling, reliable because of high quality plastic components, low maintenance cost, easy operation and long life.

Material of Gas Chlorinators :

Ragid PVC Pipe, Rod, Sheet, Copper, Brass and extra heavy duty Borosilicate Glass are used in the making of the Chlorinator.

Design Feature :

AQUA Gas chlorinators has been adopted to open design. By this, it is easier to detect possible leak in time. Due to open design, it is more spacious arrangement for all parts, easily accessible for control, adjustment and replacement / repair. Above all, disturbance in the chlorine Liquid Gas and water feed have no effect on its functioning.

Specifications :

  • Diaphragm Pressure Gauge
  • Primary Filter
  • Niddle Valve
  • PVC Bend or Copper Bend
  • Secondary Filter
  • PVC Bend with Glass Non - Return Valve
  • Mixing Chamber
  • Solution
  • Plastic Injector
  • Cylinder Connections
  • Operation

 Accessories :

Cylinder Key, Spanner, Screw Driver, Bottle of Ammonia Solution, Lead and Rubber Washer, Moisture Glass Tube, PVC delivery hos pipe, Chlorine test kit ot check up to 1 ppm. (As per quotation condition)

Precaution :

Moisture Cholrine Gas is very corrosive. So precautions are taken to exclude moisture coming into contact with metallic parts of the Chlorinator, so all parts where gas and water come in contact are made form Rigid PVC which is immune to corrosive action of wet Chlorine gas. Non-Return Valve on the top of the secondary filter will prevent water coming into the filter, it will be collected in the Glass Moisture Tube at the bottom of the filter and can be removed easily when noticed by operator.

Pressure feed Chlorinator is run by Booster Pump and Motor. If electric Power Fails, first close chlorine cylinder to avoid accident problem of Gas leakage is automatically solved by provision of lead or Rubber Washer between large contact areas at all joints.

Permit only trained and responsible personnel to handle chlorine.

For Storage : Keep container away from inflammable materials and keep in clean ventilated area.

Moisture should not enter containers.

Nover force connections that do not fit. Never use hammer to open valve. Use approved equipment.

We also supply chlorine cylinder of 50, 100 & 900 KG. CAP., chloroscope to detect Chlorine percentage in water, safety kit of chlorine cylinder / toner, breathing apperatures, bleaching doser - manual & electronic etc.

Progressive change in design may be made without notice.







Solenoid Driven Metering Pumps

Series AQUA Solenoid Driven Metering Pumps are driven by an electronic circuit comprising of PCB & electronic components of proven quality for high reliability to user.

Driven End :

Comprising of Electro magnetic solenoid unit with Class 'H' Insulation.

Control Panel :

Comprises of Analog controls for speed & Stroke length, Fuse & Pulse Indicator.

Spacer :

Unique design which separates liquid end from drive end with a drain off at the Bot tin for indication of diaphragm rapture to prevent Chemical entering in to the Drive end.

Liquid End :

Head - made of PP / PVC / SS316 or Teflon Fittings.

Key Features :

  • Gland less & leakage free diaphragm pumps
  • Solenoid driven aided by professional pulser circuitry
  • Excellent proportional control with higher turn-down ratio
  • Fixed Injection frequency (for "Model CA" - 100 SPM)
  • Adjustable volume displacement via stroke length adjustment.
  • Corrosion resistant glass filled PP housing
  • Unique spacer design for prevention of chemical entry to drive end
  • Teflon faced hyperion diaphragm for long lasting service
  • Liquid - Polypropylene (PVC / SS316 / PTFE - as optional)
  • Integrated low level switch (as optional)
  • Low power consumption
  • Modular design occupying less foot print & light weight
  • Section lift up to 1.5 m Wc
  • Steady state accuracy : /- 3%
  • Repeatability : /- 3%

Standard Material Of Construction :

Housing GFPP
Spacer GFPP
Head Polypropylen (PP)
Diaphragm Teflon faced Hypaion
Ball Glass
Suction / Discharge Fittings PVC
Injection Check Valve PVC
Foot Valve PVC
Tubing  LDPE
Elastomers Viton

Capcity Chart :

MODEL MAX. PR.
(in Kgs/Sq.Cm)
CAPACITY
(in LPH)
CA 04 06 04 06
CA 05 05 05 05
CA 01 12 01 12
CA 02 10 10 02
CA 10 02 10 02
CA 12 01 12 01

Industrial Application :

  • Chlorination
  • Water & Effluent Treatment
  • Refineries & Fertilizers
  • Pharmaceuticals
  • Chemical & Petrochemical
  • Paper & Textiles
  • Thermal Power Plants
  • Food & Beverages






Motor Driven Dosing Pumps

Series "FM" reciprocating type mechanically actuated diaphragm motor driven dosing pumps are driven by a 0.5 HP, 1440 RPM Squirrel Cage induction motor (Input Powder supply - 415 V / 3 Phase / 50 HzAC).

  • Mechanically actuated diaphragm
  • High precision balls and seal, rings for accuracy
  • Manual flow control, adjustable while running through stroke length adjustment knob
  • Composite PTFE Hypalon Diaphragm for long life
  • Motor driven worm shaft & worm wheel drive
  • Liquid end material of construction in PP (Also in SS316, PVC and Teflon on request)
  • Light weight aluminum alloy body
  • Modular design occupying less foot print
  • Steady state accuracy _ 2%
  • Repeatability _ 3%
  • Turn down ration 10:1

Standard Material of Construction :

Housing Aluminium Suction Discharge Fittings PVC
Spacer Cast Iron Pressure Relief Valve PVC
Base Frame MS Injection Check Valve PVC
Head Polypropelene (PP) Y Strainer (or) Foot Valve PVC
Diaphragm Teflon faced hypalon Tubing LDPE
Ball Glass Elastomers Viton


Capacity Chart :

Model Max Pr.
(in Lg./Sq.Cm.)
Max Capacity
(in LPH)
FM 10 15 10 35
FM 08 45 08 45
FM 08 60 08 60
FM 05 100 05 100






Vacuum Controllers

The Use of chlorine for sterilizing water is widely practiced throughout the world. Vacuum controllers (direct cylinder mounted gas chlorinator) are generally accepted as a very efficient and economical means of rendering water supplies safe to drink and giving protection against water - bone diseases.

The technique involves mixing chlorine gas and water to form hypochlorous acid. this kills the harmful bacteria and viruses.

General Specification :

AQUA -ll instrument represents the latest advance in the design of solution (Vacuum) feed gas chlorination.

Vacuum Chlorinators :

For safety reasons the system widely in use today for the purification of water supplies in a vacuum solution feed gas chlorinator. A vacuum chlorinator is much safer than a pressure chlorinator as any loss of vacuum causes the gas supply to be shut off instantly and automatically.

The principle involves mixing an auxiliary supply of water with chlorine gas. the concentrated solution of chlorine is then injected into the water.

Operation in this way, with the AQUA-ll, provides a very economic means of purifying water suppliers while maintaining a very high degree of safety and reliability.

Features :

AQUA-ll incorporates many technological advanced designed to enhance long term reliability and achieve optimum performance with minimum supervision and maintenance.

Method of Operation :

The chlorine regulator can be mounted either on a wall or on top of the gas cylinder or container.

Correct operation depends on obtaining healthy vacuum from the injector. Water flowing through the injector creates a vacuum which opens the inlet valve to admit the gas into the regulator. The injector consists of a vacuum producing venturi and a spring loaded diaphragm check valve. The gas passes through the flow meter and the rate control valve and then to injector where it is throughly  mixed and dissolved in the water and carried to the application point as a solution.

Any vacuum failure automatically shuts off the chlorine gas and ensures that no gas escapes into the atmosphere.

There is an automatic vent to atmosphere if pressure build up in the regulator.

If the source of chlorine gas is exhausted or the gas line plugged and excess vacuum valve in the regulator or the gas supply lines.

AQUA-ll gas chlorinator and injector are constructed for PVC, VICTOM, Monel, Teflon, Extra duty Borosilicate Glass, Silver and Copper Materials.

Guarantee :

For correct performance of our parts for a period of 12 months.
We also supply Chlorine Cylinder 50 & 100 Kg. Cap., Chloroscope to detect chlorine percentage in water, Safety.






Chlorine Containers

 
General Specification :

Particulars Model - VPVD - 01
Design Code Asme-Seciton-Vlll-DIV.1 Emended 2004-05.
Design Pressure 20.771 KG/SQ. CM [305 PSIG].
Design Temprature Suitable For Temp. up to 65 / 10 Degree C.
Radiography 100% for all Welded Seams, by X-Ray Machine only.
Heat Treatment Fully Stress Relieved.
Corrosion Allowance 1.6 MM [1/6"] Minimum.
Water Capacity [Approx.] 769.4 Kgs [1696.23 16s]
Chlorine Capacity [Approx.] Normal Capacity. 916 Kgs [2019.43 16s]
Approval Of Design by
  • Llyod's Register Asia.
  • Chief Controller of Explosive, Govt. of India.
Inspection By Llyod's Regiser Asia.
Materail of Construction C.C.PLATE-SA 516 GR. 70.
Shell Thickness "S" 12 MM
Dished ends Thickness "T" 14 MM [Normal]
Overall Length "L" 2060 12 MM
Diameter 774 MM ID, 798 MM OD.
Shape of Domes Concave with chime as per CFR 49. both end inward Curved.
Tare Weight 625 Kgs [1377.88 16s] Approx.
Education Pipe 1/2 " NB SCH 80

Chlorine Emergency Safety Kit (900 Kg Tonner)

Part List :

Name Of The Part
Quantity
Tie Rods 02 No.
Nut & washer 08 No.
Front Bar wotj Sq. Block 01 No.
Front Hood 01 No.
Rubber Gaskit (OD-165mm-ID-90MM) 02 No.
Chlornine Valve For Hood 01 No.
Front Hood 01 No.
Valve Cap 01 No.
Hood Pressure Bolt 01 No.
Plug Hood 01 No.
 Rubber Gaskit (OD-115MM-ID-60MM) 03 No.
Yoke 01 No.
Stud 01 No.
Cap Nut 01 No.
Dok Plate with "U" Hools 01 No.
Steel Patch Plate 01 No.
Docking Bolts 04 No.
Link Chain (96 " Long) 01 No.
Preessure Bolt 01 No.
Rubber Gasket (150 x 80 MM) 02 No.
Pressure Plate 01 No.
Rubber Gasket 02 No.
Pressure Bolt 01 No.
Drift Pins (In 2 Size) 02 No.
Yoke Clamp 01 No.
House Nipple 01 No.
Lead Washer 04 No.
Hose Clip 02 No.
Flexible Tubing 01 No.
Gas Mask (Canister Type) 01 No.
Ammonia Solution Bottle (500ML) 01 No.
Key for Valve Spindle 01 No.
 Rubber Frame Goggles 01 Nos.
Hand Gloves (PVC OR Rubbber) 01 Pairs.
Chest Apro0n 01 No.
 Hmmer 01 No.
Spanner 30 x32 01 No.
Spanner 9/16 x 11/16 01 No.
Teflon Tap 01 No.
Ammonia Torch 01 No.






Chlorine Gas Cylinders

Specification :

Chlorine Gas Cylinder Confirming To IS: 3196 [Part 4] : 2001
                                 [Supersending IS : 7681]


Model                   Gas
Capacity
[KGS]
Internal
Volume
[LTS]
Inside
Diameter
[MM]
Nominal
Wall
[KGF/CM2]
Working
Presuure
[KGF/CM2]
Test
Pressure
[KG]
Tare
Weight
[KG] 
JMC - 42C 50 42 356 6 19.9 30 40
JMC - 84C 100 84 356 6 19.9 30 65
JMC - 100C 120 100 356 6 19.9 30 75
JMC - 118C 142 118 356 6 19.9 30 82
JMC - 55C 80 55 356 6 19.9 30 36

Note :- With IS Certificate, Chlorine gas Cylinder also hve CEE, Nagpur Ceritifcate.

Chlorine Emergency Kit (100 Kg Cylinder) :

Part List :

Particulars Quantity
Main Pressure Bolt 01 No.
Wing Nuts 02 Nos.
The Rods 02 Nos.
Pressure Bolt 01 No.
Docking Bolts 02 Nos.
Pressure Plate with Gasket 01 No.
Chain 01 No.
"S" Hooks 02 Nos.
Dock Plate 01 No.
Gasket 01 No.
Hood with Valve Adapter 01 No.
Base Plate 01 No.
Nuts 2 Nos.
Top Bar 01 No.
Taper Pin 01 No.
Yoke Clamp 01 No.
Blind Npple 01 No.
Lead Washers 05 Nos.
Yoke Clamp Spanner 01 No.
M S Taper Hose Nipple 01 No.
S.S.Jubilee Clips 02 Nos.
1/2 PVC Pipe 05 Mt.
Gas Mask with Canister for Chlorine 1 St.
Amonia Solution 450 ML
Amonia Torch 01 No.
Rubber Frame Goggle 01 No.
PVC Gloves 2 Pairs.
PVC Aprons (Chest) 2 Nos.
Hammer 01 No.
Key for Valve Spindle 01 No.
Chlorine Valve 01 No.
5/8 BSP Cap Nut 01 No.
Fix Spanners 02 Nos.
Screw Driver 01 No.







Air Breathing Apparatus

For working in smoke / gaseous contamination of any degree -i or oxygen deficient areas.

Our Air Breathing Apparatus is must for Fire Fighting, Rescue Operation & Industrial Safety.

Widely used all over the country by various private and public sector undertakings.

  • Available in 30 minutes and 45 minutes duration cylinders.

Special Features :

  • Pressure Reduction System of set is as per the latest International standards
  • No assistance required for donning the set
  • The Cylinder can be changed for recharging without any difficulty
  • The brass parts are chromium plated for corrosion resistance
  • Gives audible alarm before the expiry of the time
  • The equipment is supplied in an easy to carry case

Equipment manufactured as per IS: 10245 part-II

Air Supply Cylinder : Seamless, high tensile steel cylinder manufactured to Home Office approved specification.

Cylinder Valve : Manufactured to BS/IS specification with a high tensile brass body and moulded rubber hand wheel.

Pressure Reducer : All brass construction utilising simple and well proven piston principle of operation and incorporating overload protection.

Air Hoses : Both high and low pressure hoses have stainless steel end fittings. Each hose is tested at more than twice its maximum working pressure.

Demand Valve : The demand valve operates in accordance with the wearer's inhalation and supplies air to the wearer's requirements. Exhalation is achieved through separate valve and when this takes place, the demand valve automatically closes.

Face Mask : Moulded rubber full face mask as reflex edges for perfect face seal having speech diaphragm & unidirectional exhalation valve quick release buckles for head harness provided.

Pressure Gauge : The easily readable pressure gauge calibrated in bars/PSI protected by rubber cover is connected to pressure reducer by a flexible high pressure hose line.

We can also offer you :

  • Gas Mask Respirator
  • Rope Ladder
  • Safety Helmets
  • Wind Sock
  • Glow Signs
  • Artificial Respirator
  • Spark / Flame Arrester
  • Safety Net, Safety Belt
  • Barricading Safety Tape
  • Fire Fighting Equipment
  • Fire Suit

Cylinder Strap : The carrying cylinder strap of back plate can also accommodate cylinders of all types/sizes without any modification. The infinitely adjustable camlock mechanism provides a simple, very secure, quick and fail-safe operation.

Back Plate : Made of fibre glass, which is light in weight and has chemical resistance. It is orthopaedically designed in such a manner that weight of the cylinder is put on lower portion giving comfort to the user. For easy handling / transportation, a slot has also been provided on the back plate.

Alarm Whistle : Attached to high press, j attachment which is positioned close to the ear to avoid confusion as to where whistle is sounding, giving enough time to the user to reach safe place for change over of cylinders.

Harness Assembly : Made from fine quality nylon webbing is adjustable type with quick release buckles.

Operation manual and inspection procedure will be furnished with each set.

Optional Accessories :

  • Air-line connection can be provided
  • Second user provision connection can provided




Copyright © Aqua Services, All Rights Reserved (Terms of Use)
Developed by IndiaMART InterMESH Limited
Member IndiaMART.com