We offers Numerical Over Current Relay (JNC068C).
FEATURES
• Programmable for 1A / 5 A relay rating
• 3 OC + 1 EF + 1 SEF/REF
• Choice of 6 IDMT curves and definite time
• Trip test facility
• History of 6 latest faults along with settings
• Self supervision facility
• MODBUS open protocol over RS - 485 port
• MODBUS protocol over RS - 232 port
• Draw out facility with inbuilt CT shorting
• Standard dimension - 144mm x 144mm
APPLICATION
The relay provides time graded phase and earth fault (2 stage) protection with communication facility
PRINCIPLE OF OPERATION
The relay measures the line current from each of the line CTs and if the current exceeds the set threshold, then relay extends a trip signal after an operating time. The relay's "operating time" is determined by selecting "definite time" or one of the six "inverse time" characteristics.
Input to sensitive earth fault protection can be connected in two ways. First one the residual current derived from three phase current transformers, and second is low output core balance current transformer can be connected. Input to restricted earth fault protection will be derived from neutral CT output with external stabilizing resistor.
Phase over current, Earth fault, Sensitive earth fault/Restricted earth fault protections* features can be made active or inhibit independently.
TECHNICAL DATA
| RATINGS | |
| Current rating ( In ) | 1A/5A( Site selectable) |
| Aux. Supply | 1) 20 to 60V DC |
| | 2) 80 to 260V AC / DC |
| SETTINGS | |
| Operating characteristics (Separate for Phase : | 1) 3.0s Normal Inverse |
| & Earth fault) | 2) 1.3 s Normal Inverse |
| | 3) 1.5s Very Inverse |
| | 4) 0.8s Extremely Inverse |
| | 5) 0.6s Extremely Inverse |
| | 6) 13.3s Long Inverse |
| | 7) Definite Time |
| Phase OC (IDMT) : | 50 to 200% in steps of 5% |
| Phase OC (Def time) : | 50 to 500% in steps of 5% |