We offer a wide range of 95SP6 automatic voltage regulators, which is made of precision engineered components. These sophisticated machines are designed for use with 50 / 60Hz AC Generators that helps in the operation of both solo and parallel running modes. These AVR are extremely rugged and handles high proportion of non linear loads.
Application:
- For effective reactive load sharing during the time of parallel operation the regulator produces droop with respect to kVAr loading, when fed with a CT signal from 'W Phase as required
- SES 95SP6 is capable of exciting the exciter fields upto1250 kVA when used within its input and output ratings
- Ability to pick up from very low residuals
- By use of complex internal filtering are specialties of this regulator sustain a variety of non-linear loads can be performed
The regulator can be machine or panel mounted.
- SP6-mosfet - for handling higher % of non-linear Load
- SPE6 - with Excitation Current Limiters
- SP6 (S) - with Accessory Input A1, A2
The salient features of our range of 95SP6 are listed below:
- Tested for bump, vibration and extreme environmental conditions
- One part system with built-in active and spare fuses
- Available from stock
- Economical
- Easy interconnection
- Compact, lightweight and simple
- Build-up from very low residuals
- Proven field performance on all popular makes of Alternators over a wide range of ratings
- Repairable power stage
- Suitable for solo and parallel operation
Technical Specification
1. Input Power
· Volts : 240V AC rms ±10%
· Frequency : 50/60Hz
2. Output Power:
· Volts : 95V DC at 240V AC input
· Amp : 6 amp DC 8.0 amp for 10 sec. (when allowed by field resistance)
3. Build-up : Min. 2.5V AC at V & N terminals of AVR
4. Voltage Regulation : Better than ±1% at AVR terminals
5. External Voltage Adjustment when provided: Min. ±10% around 415V (using 2K/2.5K 1W Pot)
6. Stability Adjustment : Adjustable to get steady state stability and good transient response
7. Sensing: 415 V AC, 2-line sensing. AVR senses true average of the Line-to-line waveform
8. Response Time: Less than 75 milli sec.
9. Closed Loop Response: Typically 0.5 sec. to recover to 98% of the set voltage for field forcing ratio of Response 1:2
10. Quadrature Droop at 5 amp Input from W phase: 10% max. and adjustable
11. Weight: 700 gms