We manufacturer Industrial Grade Chargers, which find its application in Hydropower plant, Sub-stations, and factories.
| Charger Type | Isolated Float cum Boost Charger with DCDB |
| AC Input | 440V +/- 15% |
| AC Input frequency | 50 Hz |
| Output Voltage | Normal 48V/110V Float Adjustable from front panel to Suite the Battery |
| Boost Adjustable from front panel to suit the Battery |
Output Current Limit Battery Charging Current Power Conversion Device | 50A/70A/110A as Required Adjustable to Suit the Battery Three Phase full Wave Controlled Rectifier PWM Active Rectification |
Voltage Regulation Efficiency Ripple Control Protection and Switch Gear | <1% for given input range >80% < 3% with battery connected Micro Processor Controlled Input- TPN MCB
Output- DP MCBs for load Battery- DP MCB Capacitor- HRC fuse Thyristor- Semiconductor fuse |
| Meter and Indication | LCD screen to display various status and Errors. |
| Equalization (Manual and Automatic) | Frequency and duration of equalization are programmable through menu. |
| Earth Fault Detection | Adjustable and can be enabled or disabled from front panel menu. |
| Diode Drop | Automatic to lower the load voltage during Boost charging or Equalization charging. |