Temperature Controller |
|
|
Engaged in manufacture and supply of temperature controllers such as temperature indicator, dual set point temperature controller, pid temperature controller, programmable pid temperature controller with digital timer, single set point temperature controller, universal temperature scanner - recorder.
|
 |
|
 |
|
|
|
Item Code: Index
We specialize in fabricating superior quality temperature indicator. The collection is developed in conformity to industry standard as well as in accordance with client specific requirements. It is featured with rugged construction, durability, long service life and low maintenance. Following are some of the specifications of our temperature indicator: - Input Version : RTD , J,K,R,S , DC Linear
- Facility to view & Store Min/Max Process Value
- Dimensions: 48x48 , 48x96, 72x72 , 96x96
- Also available in Flame Proof Enclosures certified for Gas Group IIA / IIB
Salient Features: - Single Row 4 Digit Display
- J / K / R / S, RTD Pt100 Input Versions
- Optional PV HOLD Facility with Relay Output
- Optional Serial Communication Port
- Sizes (mm): 48(H) X 48(W) X 85(D), 72(H) X 72(W) X 65(D), 96(H) X 96(W) X 65(D)
Specifications: User Interface: Display
| 4 digits, 7 Segment High Intensity Red LED
| Keyboard
| 3 Front Panel Keys
| Input: Input type
| Thermocouple J / K / R / S Version RTD Pt100, 3-Wire Version
| Accuracy
| ± 0.25% of reading, ± 1 LSD, ± 1°C
| Measuring Rate
| 5 Samples per second (sampling time 200mS)
| Corrections
| Automatic, CJC for T / C, LRC for 3-wire Pt100
| Features: Signal Conditioning
| Settable Offset for Sensor Zero-Error Removal & Digital Low-Pass Filter Process Value Averaging
| PV Hold Feature (Optional)
| Provided via Potential-free Contact Closure on Rear Terminals. Freezes the PV Updation
| PV Hold Alarm
| Relay Output. Indicates PV Hold Event.
| General: Supply Voltage
| 85 to 264V AC, 50 / 60 Hz
| Environmental
| Operating 0 to 55°C, Storage -10 to 70°C, 5 to 95 %RH Non-condensing
| Panel Sealing
| Conforming to IP 65, NEMA 4X
| Electromagnetic
| Conforming to Generic Emissions standard EN50081-2 and general immunity requirements of EN50082-2 (95)
| Safety Standard
| Conforming to EN61010, installation category 2 (Voltage transients must not exceed 2.5 KV)
| Dimensions (mm)
| 48 (H) X 48 (W) X 85 (D), 72(H) X 72(W) X 65(D), 96(H) X 96(W) X 65(D)
| Panel Cutout (mm)
| 45 (H) X 45 (W), 68 (H) X 68 (W), 92 (H) X 92 (W)
| Weight (Approx)
| 250 grams
|
|
|
|
 |
|
 |
|