Voltage Regulation Systems
Our team of experts maintain a strict vigil and runs regular checks on the quality of products that are sourced before they are dispatched like voltage regulation systems, digital tap position indicator, annuciator, rtd system, electronic hooter. Our range of products include :
|

|  |
We are engaged in providing Voltage Regulation Systems, Digital Automatic Voltage Regulating Relay, Digital Automatic Voltage Regulating Relay.
Microcontroller - based LTC Transformer and regulator control provides reliable operation and expanded capabilities.
Interfaces with conversion front panels sized to replace popular industry tapchanger controls.
Serial communication ports with several on board communication protocols.
Two active serial communication ports through RS-232,RS-485, or Fiber Optics.
Field updatable programming
Reverse power detection /operation
Demand matering
Time/date stamping of maximum /minimum system conditions.
Data logging of metered parameters.
Self-test alarm and user-programmable alarm
Line overcurrent tapchange inhibit
Transformer parallelling by circulating current method/external master follower cicultry
LDC with R & X or Z-compression.
Can be configured for various tap position ranges.
Definite or inverse Time Delay
Voltage limits with automatic runback, tap position limits.
Both 50 & 60 Hz models available
UL Listed.
|

|  |
Our Digital Tap Position Indicator are as per following specification :
Annex. A : Application,Specifications and Features of Various Models of Tap Postion Indicator
| Sl. |
Feature |
TDC 2001 |
TPC 2001 |
REP 2002 |
PX 2000 |
PX 2001 |
PX 2002 |
| 1. |
Application |
Indication of operating tap No. |
Indication of operating tap No. |
Repeat Indication of operating tap No. |
Indication of operating tap No., Voltage and count of tap change operations |
Indication of operating tap No., Voltage and count of tap change operations |
Indication of operating tap No., Voltage |
| 2. |
Mounting |
Flush Mounting |
Flush Mounting |
Flush Mounting |
Flush Mounting |
Flush Mounting |
Flush Mounting |
| 3. |
Optional Instruments |
- |
Repeater Model REP 2002 |
Repeater Model REP 2002 |
Repeater Model REP 2002 |
Repeater Model REP 2002 |
Repeater Model REP 2002 |
| 4. |
Tap Range |
1 -70 positions |
1 -70 positions |
1 -70 positions |
1 -70 positions |
1 -70 positions |
1 -70 positions |
| 5. |
Auxiliary Supply |
110-230V AC or 90-270V AC/DC |
90-270V AC/DC |
90-270V AC/DC |
90-270V AC/DC |
90-270V AC/DC |
90-270V AC/DC |
| 6. |
Output |
- |
One Output 4 -20 mA |
Optional |
One Output 4 -20 mA |
One Output 4 -20 mA |
One Output 4 -20 mA |
|

|  |
Our Automatic Power Factor Control are as per following specification :
PF Target Power Factor (1.70 to 1.00)
PF Cap / Ind : Lagging /Leading Target Power Factor.
Dead band : Dead band for target Power Factor (0.00 t0 0.30). Corr. Delay : Capacitor - switching delay (1 to 250).
Ct Rating 1A / 5A : Current rating for the current transformer/ (select 1 AMP if the CT input is received through the select 5Amp if the CT input is received through the R5 pin of the power connector).
Ct Ratio : turns ratio for the current transformer (1 to 200)
Program No : Program No. ( 1 to 33) (refer the program no. chart).
CB1 KVAr : KVAr rating of the first Capacitor Bank connected (0.5 to 99.5 KVAr)
Change password : Change password (0000 to 9999)
Enter Password : Enter Password (0000 to 9999)
Wrong Password : Incorrect Password.
ONLINE MODE MESSAGES :
OverVtg : Over Volatage.
UnderVtg : Under Voltage
UnderCurr : Under Current
OvercComp : Over Compensation
UnderComp : Under Compensation
Ct. conn : Incorrect CT Connetion
|

|  |
We are offering Annuciator. Our Alarm Annunciator is as per following specification :
Annuciator Model Features
| Sl. |
PSS 400 |
PSS 500> |
PSS 401 |
PSS 350 |
|
PSS 351 |
PSS 352 |
PSS 353 |
PSS 400 |
| 1. |
System Content |
ANN |
ANN |
ANN |
ANN |
ANN |
ANN |
ANN |
ANN |
| 2. |
Overall dim |
96 X 96 X 150 |
260 X 145 |
220 X 170 |
220 X 170 |
220 X 170 |
170 X 220 |
170 X 220 |
285 x 140 |
| 3. |
Cutout |
92 X 92mm |
230 X 145 |
205 X 155 |
205 X 155 |
205 X 155 |
155 X 205 |
155 X 205 |
285 X 140 |
| 4. |
Window Size |
30 X 40mm |
25 X 60 |
45 X45 |
45 X45 |
45 X45 |
45 X45 |
45 X45 |
45 X45 |
| 5. |
No. of Windows |
14W |
6 -8 W |
9 - 10W |
1 - 8W |
1 -12W |
1 - 12V |
1 -8WV |
1 - 20W |
|

|  |
Digital Temperature Scanner are as per following specification :
| Temperature Sensor |
RTD (Pt 100 DIN 43760) |
| Number of Sensor Inputs |
6 Nos. or 8 Nos. Max |
| No. of Set Points |
2 Nos. + 2 Nos. optional |
| Resolution |
1oC or 1oC Opt. |
| Accuracy |
+- 0.5% of F.S. |
| Dead Band (Hystersis) |
User Settable (0 to 9 oC |
| Display Scan Time |
Seven segment,12.5 mm RED LED 1 digit display for channel no 4 digit display for temperature |
| Error Setting |
+-10oC |
| Indications (additional) |
a) RED LED to indicate Power Onb) Yellow LED Auto Manual c) Green
LED Alarm (relay) d) Green LED for very high (Relay)f)Green LED for Fan
(Relay) g) Blue LED for sensor Fault |
| Overall Size |
96 X 96 X 150 |
| Cutout Size |
92 X 92 X 150 |
Electrical
| Supply Voltage |
90 V to 260 V AC/DC Voltage |
| Output |
Two N/O Contacts (5A at 240V AC or 10A at 110V AC |
| Analog Output |
One analog o/p 4-20mA, 1k burden one analog o/p 4-20mA, (Optional) |
| Terminals |
Screw Caged suitable for 0.2 - 4 sq.mm. solid conductors |
| Insulation |
Insulation resistance > 100 M at 500 V DCbetween each Terminal
proof between all mains supply terminals shorted together & earth -
no break down for one minute. - Factory tested at 1.5 kV rms, 50 Hz. -
Susequent field test at 0.5 rms, 50 Hz |
|

|  |
We are offering RTD System as per client specification. Following are given some features :
Annex. B : Features of various Models of RWTI Series RTD-100/W
| Sl. |
Feature |
RTD 2000 |
RTD 2000 A |
RTD 2000 B |
RTD 2000 C |
RTD 2000 D |
| 1. |
System Content |
Pt.100 sensor, Shunt resistor box & indicator with inbuilt CCU |
Pt 100 sensor, shunt resistor box & indicator with inbuilt CCU |
Pt.100 sensor, Shunt resistor box & indicator with inbuilt CCU |
Pt.100 sensor, Shunt resistor box & indicator with inbuilt CCU |
Pt.100 sensor, Shunt resistor box & indicator with inbuilt CCU |
| 2. |
Overall Dim. |
96 X 96 X 150mm |
96 X 96 X 150mm |
96 X 96 X 150mm |
96 X 96 X 150mm |
96 X 96 X 150mm |
| 3. |
Panel Cutout |
92 X 92mm |
P92 X 92mm |
92 X 92mm |
92 X 92mm |
92 X 92mm |
| 4. |
Mounting |
Flush Mounting |
Flush Mounting |
Flush Mounting |
Flush Mounting |
Flush Mounting |
| 5. |
Display |
3 digits,7 segment LED 12.7 mm ht. |
3 digits,7 segment LED 12.7 mm ht. |
3 digits,7 segment LED 12.7 mm ht. |
3 digits,7 segment LED 12.7 mm ht. |
3 digits,7 segment LED 12.7 mm ht. |
| 6. |
Temperature Range |
0-150o C (STD)temp.can be set - 50 500oC |
0-150o C (STD)temp.can be set - 50 500oC |
0-150o C (STD)temp.can be set - 50 500oC |
0-150o C (STD)temp.can be set - 50 500oC |
0-150o C (STD)temp.can be set - 50 500oC |
|

|  |
Salient Features :
The microprocessor based, model - WTC 2002 / OTC 2003 is distinguished for its features, construction, operation and cost effectiveness. The Versatility of this model is a result of careful consideration and understanding of the wide spectrum of the user needs and convenience, whether during testing or online operation.
This instrument is designed using state of the art integrated circuits (IC), and glass epoxy Circuit Boards (PCB). Remote Winding Temperature is easy to configure this instrument as the same is very user friendly. The instrument incorporates a stabilized power supply and filter circuit for absorbing power supply transients, thus ensuring accurate control / and a stable disply. The out put is displayed and has a viewing distance of more than 4 meter.
BURN - IN : Each instrument is tested and aged at ambient conditions for 48 hours in electrically energized condition prior to delivery as per Pradeep's norms for verification of design reliability. This practice ensures the unit's continued performance to specifications and to customers satisfaction.
Type Tests :
Repeated series models are type tested at ERTL (West), STQC, Govt of India for following :
EMC Test : As per IEC - 61000 - 4 - 2 : 1995 for ESD and for HED.
Impact Shock Test as per IS 9000 ( Pt.VII) : 1997.
Cold and Dry Heat Test as per IS 9000 (Pt.II) : 1997.
Additional important Features :
a. Range can be set lower side and higher side.
b. Having the facility of Error Setting to compensate the line drop or hold.
c. Having the facility of 4-20 mA output optional on demand. d. Having the facility to check all the segments by pressing "SET" Key.
|

|  |
Our Electronic Hooter are as per following specification.
Features
High Audio Output : 90 to 125 dB
Single supply : 12V AC/DC, 24V AC/DC, 48V AC/DC,
110 VAC, 230 VAC
or Univeral Supply : 24 - 240 V AC/DC
Din standard (96 X 96 X 65 mm) Panel / Wall mounting.
Cut-out 92 (W) X 92 (H) mm
Tone & Volume Adjustable
Custom Models with multiple tones / Musical tones
|

|  |
Our Current Converter Unit are as per following specifications:
Annex.A :Features of Various Model of RTT - 3000
| Sl. |
Features |
CCUPT 203 |
CCUO 201 |
CCUT 202 |
| 1. |
Application |
Measurement of Winding Temperature |
Measurement of Top Oil Temerature |
Incication of operating Tap no. of transformer fitted with OLTD |
| 2. |
System Contents |
Sensor with PT- 100 insert & heater Shunt resistor unit Current Converter Unit (CCU) |
Sensor with PT -100 insert Current Converter Unit (CCU) |
Current Converter Unit (CCU) |
| 3. |
Mounting |
Rail Mounting |
Rail Mounting |
Rail Mounting |
| 4. |
Temperature Range |
0 - 150 deg. c However temp. range can be set up to -50 deg to 400 deg. C if required |
0 - 150 deg. c However temp. range can be set up to -50 deg to 400 deg. C if required |
N.A |
| 5. |
Auxiliary Supply |
90 - 260 V ac/dc |
90 - 260 V ac/dc |
90 - 260 V ac/dc |
| 6. |
Output |
Two outputs 4 - 20 mA at 500 mA at 500 Ohm burden each |
Two outputs 4 - 20 mA at 500 mA at 500 Ohm burden each |
Two outputs 4 - 20 mA at 500 mA at 500 Ohm burden each |
|

|  |
Product Description
The series current transformer CT can be applied to test, control, display and record the running of the equipment against the damage in the AC circuit with the running of the electrical equipment, and to protect the equipment against the damage in the AC circuit with the rated voltage below 600V and the frequency of 50/60Hz. The products can be also applied to from a complete set of mine transformer.
|

|  |
Digital Servo Voltage Stabilizer Control Card, Digital Servo Voltage Control Module is equipped with an advanced Microcontroller Technology with self-controllable Design. It requires minimum external wiring for fast production of Servo Voltage Stabilizers.
The Main Features:
Display Module: To display the input and output voltages simultaneously.
Protection: The output voltage is disconnected, incase the feedback to the control card is disconnected or loose connected.
Programming: The Stabilizer Control Card can be programmed for the below parameters:
Low voltage cut off set Display shows-Lo
High voltage cut off set Display shows-Hi
Time delay relay set (TDR) Display shows-tdr
Hysteresis Display shows-HYS
Low Voltage cut off: This value can be changed from 160V to 210V. Whenever there is any fluctuation present in the power supply to the extent that output voltage has turned out to be below this set voltage range then relay switches OFF.
High Voltage cut off: This value can be changed from 220V to 254V. Whenever there is any fluctuation present in the power supply to the extent that output voltage has turned out to be above this set voltage range then relay switches OFF.
Time Delay Relay: This value can be programmed from 15 sec to 180 sec. Whenever the output voltage goes beyond the low and high voltage range, the relay switches off. When the output voltage has reached in this range and now this much time (which has been programmed in TDR) is introduced and after this the relay turns ON.
|

|  |
(Item Code: Local-Winding-Temperature-Indicator) The Temperature time constant of heater assembly is almost same as that of transformer winding and hence response to the change of transformer winding temperature by heater and in turn instrument is fast.
| Specifications |
| Actual temperature display ch 1 WTI) |
3 digit, 0.5 inch high, 7 segment red LED |
| Temperature range |
0 - 150 deg. C |
| Resolution |
1.0 deg. C |
| Actual temperature display ch 2 WTI) |
3 digit, 0.5 inch high, 7 segment red LED |
| Temperature range |
0 - 150 deg. C |
| Resolution |
1.0 deg. C |
| Output |
| 4 - 20 mA analogue output 1 |
4 - 20 ma analogue output 1 corrosponds to to - 0-150 deg. C |
| 4 - 20 mA analogue output 2 |
4 - 20 ma analogue output 1 corrosponds to to - 0-150 deg. C |
| Relay Settings : |
| Set 1 to Set 10 Temp. Display |
Pair of 3 digit, 0.5 inch high, 7 segment red LED for High and Low Setting |
| Temperature setting range |
1- 150 deg. C |
| Operating ambient temperature |
0- 150 deg. C |
| Power Supply |
90 V to 260 V ac / dc |
|
|
|