Standard Distribution Transformer 15 KVA to 1000 KVA
STMC Make transformers are designed and tested as per IS : 2026, BS - 171, IEC - 76 & IEC - 726.
Vector Group
Transformers will be connected as per vector group reference Dyn 11. Other vector groups can be offered as per specific requirements.
Terminal Arrangement
H. V - Bare Bushings or Cable Box, L. V-Bare Bushings or Cable Box. Disconnecting
Temperature Rise
STMC Make transformers are designed for a maximum temperature rise of 40/50 degree C of oil/winding. Lower temperature rise can be offered on request.
Core
The core is constructed from low loss, cold rolled, grain oriented, annealled lamination of electrical sheet steel conforming to the latest international standards. Special frame is built-in-house for clamping the core to reduce the magnetic noise as well as making the whole structure rigid and robust.
Windings
Coils are wound with electrolyte high conductivity paper covered or synthetic enamelled copper conductors. Cooling ducts are provided to keep the hot spot temperature as low as possible. Coils are dried in electric ovens. Rigid connection support and coil clamping is provided to ensure high shot circuit strength.
Insulation
Pre compressed board Senapathy Whiteley Board and Raman Board insulation paper of best quality is used.
Tapping
A. OFF CIRCUIT TAP CHANGING SWITCH Tappings from + 5% to - 5% in steps of 2.5% for HV variation or as per customer's requirement.
B. ON LOAD TAP CHANGER 16 steps OLTC for HV variation from + 5% to - 15% in steps of 1.25% or as per specific requirements. OLTC for remote/auto/parallel operation can also be offered.
Oil
Oil is tested for resistively, dielectric and acidic characteristic conforming to IS - 335. Before topping up oil is filtered thoroughly.
Tanks
The tanks are made of M.S. steel plates / sheets with adequate bracing & stiffness. Tanks are pressure tested to withstand any type of inside or outside pressure. All the external surfaces are given a primary coat of zinc chromate, red oxide and two finishing coats of grey paint. The inner surfaces are given a coat of heat and oil resisting paint
Quality Control and Routine Tests
All STMC make transformers undergo rigorous quality control checks and are routine tested as per IS in our fully equipped laboratory. Any specific test required by the customer can also be arranged.
Standard Fittings:
-
Rating and diagram plate. -
Earthling terminals - 2 Nos. -
Lifting lugs -
Oil level indicator (Plain) -
Drain-cum bottom filter valve with plug. -
Oil filling hole with plug on conservator. -
Oil conservator with drain plug. -
Air release plug. -
Silica gel air breather. -
Bi-directional flat | -
HV terminals-outdoor bushings. -
LV terminals-outdoor bushings. -
Radiators. -
Filter valve with plug. -
Thermometer pocket. -
Oil temperature indicator. -
Externally operated off circuit tap changing switch. -
Explosion vent. -
Sampling valve (for 2000 KVA and above transformers only) |