We manufacture Starters that are designed for use on Voltages. We offer these at very affordable prices.Our range is widely used in various industrial and commercial sectors and deliver flawless performance.
|
| Auto Transformer Starters Our
range of hand operated oil immersed auto transformer starters is
compact, totally enclosed with gasketted
joints. The entire range is made of top-quality raw material and is
available at very economical prices. The team of professionals ensure
that the starters are well finished and perform smoothly. Our range includes:
- Fully automatic auto transformer starters upto 600 HP 550V (275 HP Type Tested from ERDA Vadodara.
- Manual auto transformer starters upto 200 HP 550V
- Any other voltage can be supplied on request.
Features:
- Case
and lid are of MS sheet thus suitable
for use in places demanding a robust apparatus.
- In case thermal overload rely is required it can be supplied on request.
- Adjustable
magnetic type overload protection with oil dash-pot type time lag
device provides insurance against motor burnout.
- Are
designed for ordinary duty
- Standard
trappings' are provided at 50%, 60% and 80% of the line voltage
- Correct
sequence device rendering it impossible to put the handle into the
"Running" position without going through the "Start"
position.
- Tripping
by push button fitted on the unit.
- Remote
stopping is possible by push button station or any other tripping
device—for which the no-volt terminals are brought out.
- Provision
for fitting an isolator — interlocked with the unit—so that
opening of the unit is not possible till the isolator is made "Off".
- Padlocking
arrangement for isolator.
- Cable
sealing boxes can be supplied for under-
- Ground
paper insulated cables hence suitable for PVC cable entry.
- Can
be mounted on unit type bus bar chambers to form a switchboard.
- SM AT 50 units can be wall-mounting as well as floor-mounting types. AX-45
is floor-mounting type only.
- The
unit has the provision for fitting one instrument directly on
itself. For more than one unit, an instrument panel is provided.
- Floor
stand can be supplied as an optional item.
|
Soft Starters Our
range of soft starters is a general purpose AC motor soft starter
industrial package. It provides a complete and effective AC motor
starting and protection solution with it's GPH starters built for
ruggedness and reliability. These are designed for simple and fast
installation and start-up, requiring only input power and output
motor connections. The use of superior quality raw material makes the
entire range more desirable. Applications:
- Pumps
- Fans
/ Blowers
- Conveyors
- Compressors
- Agitators
- Crushers
- Saws
Features:
- 5
- 150HP at 230V and 10 - 300HP at 460V
- Wall
mount enclosure suitable for dusty, wet or outdoor applications
- Circuit
breaker with door mounted operator provides built-in short circuit
protection and input power disconnect
- Automatic
bypass contactor
- Fused
Control Power Transformer (CPT)
- Start
and Stop Pushbuttons and Run and Fault Pilot Lights on the front
cover
- Terminals
for 2 or 3 wire remote Start/Stop
- Keypad
with protective cover mounted on enclosure door
- All
parameter changes are through the cover-mounted keypad.
- Dust
and water stay out of the enclosure.
- Monitoring
of current, voltage, kVA and kW can be done from the outside.
- AC3
rated bypass contactor and motor overload relay is standard on 5 -
30HP / 230V and 10 - 75HP / 460V
Optional
Features:
- Keypad
mounted inside enclosure
- No
circuit breaker
- Legs
for free standing enclosure
- AC3
rated bypass contactor with motor overload relay
- 575V
units are available.
| |
| Stator Rotor Starters We manufacture Oil Immersed Stator-Rotor Starters that are designed for use on Voltages up to 550 Volts. H.P. 330 HP. These starters comprise of separate Stator Controlling OCB and Rotor Controller mounted on the same base frame made of galvanized steel making it durable and efficient in working. We offer these at very affordable prices. Operating Mechanism :
- Is interlocked with Rotor Controller and the OCB cannot be switched ON until and unless the full external resistances are inserted in the circuit
- The Rotor Controller and OCB are connected strictly as per the circuit diagram
- The OCB is closed by putting the handle to "ON" position
- The push button provided with the Rotor Controllers is kept pressed till the resistance cutting "wheel" of the Rotor Controller is rotated to full "ON" position.
Contacts :
- The Stator Controlling OCB's are provided with heavy type copper contacts to ensure a trouble free life
- The contacts are made from hard drawn electrolytic copper strips
- Each unit is provided with two sets of contacts : arcing contact and main contact
- The arcing contacts make before and break after the main contacts, thus confining burning to the arcing contacts
- The main contact scarcely calls for replacement where as the arcing contact can be replaced very easily
Protection:
- Overload Protection - is of magnetic type with oil dash pot time lag arrangement in all three phases.
- Under Voltage Protection - is provided by a closing type solenoid coil.
Accessories:
- Are generally provided with incoming and outgoing cable entry plates
- Cable boxes for paper insulated cables, fully interlocked isolator and ammeter can also be provided, on request
Rotor Controller:
- Is designed to comply with latest IS for use in Rotor Circuit of A.C. Slipring Motor
- Adequately rated resistance wires are selected as per the current at various steps and are robust in design
- The Rotor resistance is based on the Rotor Volts and Rotor Amps of the Motor
- The cutting off resistances are achieved by the rotation of CAM operated "wheel" and this provides smooth starting of the motor.
Special Features:Foolproof interlocks are provided in the Starter as per the following :
- The Motor can be started only when full Rotor resistance is in the Rotor Circuit. Otherwise the Stator controlling OCB will not close.
- The motor cannot be left running with rotor resistance in the circuit. If by any chance the rotor resistance is left in the circuit the starter will trip no sooner the push button on the rotor controller is released.
|
Automatic Star Delta Starters We supply our top quality automatic air break star delta starters type CSD/A for starting of squirrel cage induction motors. These comply to BSS 775 and BSS 587 and are suitable for 40 starts per hour. The product is offered at reasonable prices. Construction:
- Totally enclosed, in a deep-drawn sheet metal casing, wall mounting type, suitably gasketted to make it dust proof
- The entire starter assembly (which is mounted on a steel plate) can be taken out of the casing by removing four screws only.
- Maintenance is facilitated by taking the interior out for repair while a spare interior can be inserted.
Rating:
- The automatic star delta starters are ideal for controlling motors upto 40 HP at 400/440 volts or 500/550 volts
- Adjustable Timer is incorporated for automatic changeover from Star to Delta.
Protection:
- Are provided with magnetic type overload releases with an adjustable oil dashpot time lag device on all the three phases
- The magnetic overload device, which works on the magnetic principle of current, is totally independent of the ambient temperature, provides a positive and direct protection to the motor
- Non-aging properties inherent to the magnetic overload device ensures the same protection to the motor even after years of service
- Can also be fitted with thermal type bi-metallic overload releases with temperature compensation devices
- The overload device is of the Hand-Resetting type which is an essential feature where remote control is required.
- The under voltage protection is inherent
Control:
- Start and Stop/Reset Push Buttons are provided on the front cover
- Remote control terminals are also provided for remote operation by means of limit switch, float switch, pressure switch or a separate push button unit.
Isolator:
- A rotary type triple pole air break isolating switch can be provided on starters, the operation of which is interlocked with the lid of the starter
- Ensures that the starter lid cannot be opened till the isolator is in the OFF position.
Cable arrangements:
- Units are provided with entries for conduit connections
- Sealing boxes can be provided for underground paper-insulated cables.
Earthing:
- Double earthing terminals are provided.
Timer:
- Special current activated change-over Timer ensures transition from Star to Delta at approximately the rated current of the motor only, irrespective of the transition time which depends on the drive
- This leads to no wear on the contacts due to transition kicks.
| |
| Automatic Combined Stator We
supply fully automatic combined stator and rotor starters type PRS that
comprise of an air break contactor with over current and under
voltage protection for the stator and set of accelerating contactor
along with automatic timing devices. These enable the motor to run
up-to the speed in a pre-determined time. These are manufactured to
conform to IS : 13947 Part-1 section 4 quality standards and are normally
suitable for 15 operations per hour. Contactor: Air break contractor confirming AC III Timers: Electronic timers to adjust no of steps and time delays. Overload
Relay:
- Can
be provided with either electro-magnetic oil dash pot time lag over
current release or bimetallic type thermal relays
- Give
the necessary inverse time characteristics for protecting the
connected equipment
Resistance
unit:
- Can
be either of nichrome round or fiat strip or cast stainless steel
grids
- Stainless
steel grids are given for units above 100 HP
- Wire
wound resistances are supplied fro lower HP
Controls:
- Start,
Stop and Reset push buttons, are provided on the front cover
- Terminals
are also provided for remote operation by outside signals.
Isolator:
- Can
be fitted quick make and quick break isolators
- Its
operation can be interlocked with the front cover.
Instruments
and Cable Arrangements:
- Provision
is made for mounting metering instruments
- Blank
gland plates are provided for fixing cable glands
Rating:
- Standard
ratings are up 40 HP to 400 HP at 415V and 2000 HP at 6.6KV
- Specific
details regarding rotor volts and rotor currents should be supplied
with the inquiries.
|
Star Delta Starters & Circuit Breakers We
offer star delta starters
and circuit breakers type SMSD-50/SMSD-200 that are designed for use on Voltages
up to 550V. The starters and breakers are designed in both
standardized as well as per client's specifications. The use of
high-grade raw material further ensure world- class products. Rating:
- Star-delta
— 225 H.P.
- Direct-on-line
— 150 H.P. on request
- Circuit
Breaker — 400 amps.
Construction:
- Main
body and the oil tank of sheet metal
- Enclosure
is both moisture and dust proof
Operating
Mechanism:
- Have
a standard 'fixed' handle but can be provided with free handle as
well
- Free
handle is a standard feature with circuit breakers.
Contacts:
- Are
provided with heavy type copper contacts made from hard drawn
electrolytic copper sections to provide trouble free life
Protection:
- Overload
protection - is of magnetic direct acting type with adjustable oil dashpot time
lag arrangement
- Provides
positive protection against single phasing being connected in phase
circuit.
- Under
voltage protection- is provided by a closing type solenoid coil.
Accessories:
- Are
provided with incoming and outgoing cable entry plates
- Cable
boxes for paper insulated cables, fully interlocked isolator,
ammeter, voltmeters, earth leakage relay, bus bars, single phasing
preventer, remote stop provision, floor stands, etc., can also be
provided on request
- Starter
& OCB are supplied without 1st Filling of oil.
| |
|