Have a requirement?
Get Best Price
Have a requirement?
Get Best Price
Products & Services
- Temperature Sensor E52
- Temperature Sensor E52
- Humidity Sensor, Temperature/Humidity Sensor ES2-HB / THB
- Digital Temperature Controller E5GC
- Digital Temperature Controller E5CC, E5CC-U
- Digital Temperature Controller (48 x 96 mm) E5EC
- Digital Temperature Controller (96 x 96 mm) E5AC
- Digital Temperature Controller E5DC
- Programmable Temperature Controller E5CC-T
- Programmable Temperature Controller E5AC-T
- Advanced Digital Temperature Controller (48 x 48 mm) E5CN-H
- Advanced Digital Temperature Controller E5AN-H, E5EN-H
- Digital Controller E5AR
- Digital Controllers E5ER
- Programmable Digital Controller E5AR-T
- Programmable Digital Controller E5ER-T
- Temperature Controllers E5CS
- Basic-Type Digital Temperature Controller (48 x 24 mm) E5GN
- Basic-Type Digital Temperature Controller (48 x 48 mm)E5CN
- Basic-Type Digital Temperature Controller E5AN, E5EN
- Programmable Temperature Controller E5CN-HT
- Digital Temperature Controllers
- Temperature Controllers E5CSV
- Digital Temperature Controller E5AC-800
- Digital Temperature Controller E5CC-800
- Digital Temperature Controller E5EC-800
- Programmable Temperature Controller E5AN-HT, E5EN-HT
- Temperature Controller E5C2
- Electronic Thermostat E5L
- Temperature Controllers E5CSL / E5CWL / E5EWL
- Modular Temperature Controller EJ1
- Modular Temperature Controller E5ZN
- Device Net Communications Unit E5ZN-DRT
- CJ Series Temperature Control Unit CJ1W-TC
- CX-Thermo Support Software EST2-2C-MV4
- ThermoTools Support Software ESTT
- Temperature Sensor E52-THE5A / 6D / 6F
- Infrared Thermosensor ES1B
- Infrared Thermo Sensors ES1C
Temperature Controllers
Temperature Sensor E52
Get Latest Price
Sheathed Platinum Resistance Thermometers
Element type | Pt100 |
---|---|
Class | JIS class B |
Sheath material | SUS316 (E52-P[]AY) ASTM316L (E52-P[]B-N, E52-P[]C-N) |
Sheath outer diameter | 3.2 dia., 4.8 dia., 6.4 dia., 8 dia |
Conductor type | 3-conductor system |
Temperature range | -200°C to 450°C (in dry air) |
Standard Platinum Resistance Thermometers
Element type | Pt100 |
---|---|
Class | JIS class B (See note 2.) |
Protective tubing material | SUS316 |
Conductor type | 3-conductor system |
Temperature range | 0°C to 450°C (in dry air) |
2. Be sure that the thermometer is free of vibration or shock if high temperatures are measured.
Sheathed Thermocouples
Element type | K (CA), J(IC) |
---|---|
Class | JIS class 2 (0.75) |
Thermal contact | Non-grounded type |
Sheath material | CA: ASTM316L |
IC: ASTM316L |
View Complete Details
Temperature Sensor E52
Get Latest Price
Exclusive ModelsThermocouplesThermocouples for Molding MachinesE52-CA2GVY, E52-IC2GVY
Element type | K (CA), J (IC) |
---|---|
Element diameter | 1.0 mm (single wire) |
Class | Class 2 (0.75) |
Protective tubing material | SUS304 |
Thermal contact | Grounded type |
Temperature range | 0°C to 350°C |
Lead wire | 0°C to 180°C |
Thermocouples with Crimp TerminalsE52-CA1GTY, E52-IC1GTY
Element type | K (CA), J (IC) |
---|---|
Element diameter | 0.65 mm (single wire) |
Class | Class 2 (0.75) |
Thermal contact | Grounded type |
Temperature range | 0°C to 300°C |
Lead wire | 0°C to 150°C |
Terminal shape | Y-type crimp terminal for M3.5 |
Platinum Resistance ThermometersPlatinum Resistance Thermometers for Surface Temperature MeasurementE52-P2GSY
Element type | Pt100 |
---|---|
Class | Class B |
Protective tubing material | SUS304 With brass-nickel-plated bracket |
Conductor type | 3-conductor system |
Temperature range | -50°C to 250°C |
Lead wire | -50°C to 150°C |
View Complete Details
Humidity Sensor, Temperature/Humidity Sensor ES2-HB / THB
Get Latest Price
Humidity Sensor section | High-polymer resistive | |
---|---|---|
Humidity detection range | 20 to 95% | |
Humidity detection accuracy | ± 3% (25 °C, 40 to 80%) | |
Power supply voltage | 24 VDC *1 | |
Operating voltage range | 85% to 110% of power supply voltage | |
Current consumption | 10 mA max. | |
Humidity output | 1 to 5 V (for humidity of 0% to 100%) Permissible load impedance: 100 kΩ min. (Use a 1:1 connection when connecting to an E5CC/E5EC/E5AC.) | |
Temperature Sensor Section *2 | Platinum resistance thermometer | |
Temperature detection range | 0 to 55 °C | |
Temperature output | Pt100: 3 wire *4 | |
Class | JIS class B | |
Communications cable length | 5 m | |
Operating temperature and humidity range *3 | 0 to 55 °C, humidity of 95% max. | |
Storage temperature and humidity range *3 | -20 to 60°C, humidity of 95% max. | |
Degree of protection | IP 20 equivalent | |
Weight | ES2-HB: Approx. 41 g (excluding cables) ES2-THB: Approx. 43 g (excluding cables) |
View Complete Details
Digital Temperature Controller E5GC
Get Latest Price
Ratings
Power supply voltage | A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC | |
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | 5.9 VA max. at 100 to 240 VAC, and 3.2 VA max. at 24 VAC or 1.8 W max. at 24 VDC | |
Sensor input | Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Analog input Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V | |
Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/THB.) | |
Control method | ON/OFF control or 2-PID control (with auto-tuning) | |
Control output | Relay output | SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value) |
Voltage output (for driving SSR) | Output voltage 12 VDC ±20% (PNP), max. Load current: 21 mA, with short-circuit protection circuit | |
Linear current output | 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: Approx. 10,000 | |
Auxiliary output | Number of outputs | 1 or 2 (depends on model) |
Output specifications | SPST-NO relay outputs, 250 VAC, 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value) | |
Event input | Number of inputs | 1 or 2 (depends on model) |
External contact input specifications | Contact input ON: 1 kΩ max., OFF: 100 kΩ min. | |
Non-contact input ON: Residual voltage 1.5 V max.; OFF: Leakage current 0.1 mA max. | ||
Current flow: approx. 7 mA per contact | ||
Setting method | Digital setting using front panel keys | |
Indication method | 11-segment digital displays and individual indicators Character height: PV: 10.5 mm, SV: 5.0 mm | |
Multi SP | Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations, or serial communications. * |
View Complete Details
Digital Temperature Controller E5CC, E5CC-U
Get Latest Price
Ratings
Power supply voltage | A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC | |
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | Models with option selection of 000:5.2 VA max. at 100 to 240 VAC, and 3.1 VA max. at 24 VAC or 1.6 W max. at 24 VDC All other models: 6.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC | |
Sensor input | Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Analog input Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, 0 to 10 V,or 0 to 50 mV (The 0 to 50 mV range applies to the E5CC-U only for those manufactured in May 2014 or later.) | |
Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/THB.) | |
Control method | ON/OFF control or 2-PID control (with auto-tuning) | |
Control output | Relay output | E5CC: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value) E5CC-U: SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value) |
Voltage output (for driving SSR) | Output voltage: 12 VDC ± 20% (PNP), max. load current: 21 mA, with short-circuit protection circuit | |
Linear current output | 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 | |
Auxiliary output | Number of outputs | E5CC: 3 E5CC-U: 1 or 2 (depends on model) |
Output specifications | SPST-NO relay outputs, 250 VAC, Models with 1 or 2 outputs: 3 A (resistive load), or Models with 3 outputs: 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value) |
View Complete Details
Digital Temperature Controller (48 x 96 mm) E5EC
Get Latest Price
Ratings
Power supply voltage | A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC | |
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | Models with option selection of 000:6.6 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC All other models: 8.3 VA max. at 100 to 240 VAC, and 5.5 VA max. at 24 VAC or 3.2 W max. at 24 VDC | |
Sensor input | Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Analog input Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V | |
Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/THB.) | |
Control method | ON/OFF or 2-PID control (with auto-tuning) | |
Control output | Relay output | SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value) |
Voltage output (for driving SSR) | Output voltage: 12 VDC ± 20% (PNP), max. load current: 40 mA, with short-circuit protection circuit (The maximum load current is 21 mA for models with two control outputs.) | |
Linear current output | 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 | |
Auxiliary output | Number of outputs | 4 |
Output specifications | SPST-NO. relay outputs, 250 VAC, Models with 4 outputs: 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value) | |
Event input | Number of inputs | 2, 4 or 6 (depends on model) |
External contact input specifications | Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. | |
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. | ||
Current flow: Approx. 7 mA per contact | ||
Transfer output | Number of outputs | 1 (only on models with a transfer output) |
Output specifications | Current output: 4 to 20 mA DC, Load: 500 Ω max., Resolution: Approx. 10,000 Linear voltage output: 1 to 5 VDC, load: 1 kΩ min., Resolution: Approx. 10,000 | |
Remote SP input | Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 Ω max.) Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 MΩ min.) |
View Complete Details
Digital Temperature Controller (96 x 96 mm) E5AC
Get Latest Price
Ratings
Power supply voltage | A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC | |
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | Models with option selection of 000:7.0 VA max. at 100 to 240 VAC, and 4.2 VA max. at 24 VAC or 2.4 W max. at 24 VDC All other models: 9.0 VA max. at 100 to 240 VAC, and 5.6 VA max. at 24 VAC or 3.4 W max. at 24 VDC | |
Sensor input | Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Analog input Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V | |
Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/THB.) | |
Control method | ON/OFF or 2-PID control (with auto-tuning) | |
Control output | Relay output | SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value) |
Voltage output (for driving SSR) | Output voltage: 12 VDC ± 20% (PNP), max. load current: 40 mA, with short-circuit protection circuit (The maximum load current is 21 mA for models with two control outputs.) | |
Linear current output | 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 | |
Auxiliary output | Number of outputs | 4 |
Output specifications | SPST-NO. relay outputs, 250 VAC, Models with 4 outputs: 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value) | |
Event input | Number of inputs | 2, 4 or 6 (depends on model) |
External contact input specifications | Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. | |
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. | ||
Current flow: Approx. 7 mA per contact | ||
Transfer output | Number of outputs | 1 (only on models with a transfer output) |
Output specifications | Current output: 4 to 20 mA DC, Load: 500 Ω max., Resolution: Approx. 10,000 Linear voltage output: 1 to 5 VDC, load: 1 kΩ min., Resolution: Approx. 10,000 | |
Remote SP input | Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 Ω max.) Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 MΩ min.) |
View Complete Details
Digital Temperature Controller E5DC
Get Latest Price
Ratings
Power supply voltage | A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC | |
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | 4.9 VA max. at 100 to 240 VAC, and 2.8 VA max. at 24 VDC or 1.5 W max. at 24 VDC | |
Sensor input | Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Analog input Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V | |
Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/THB.) | |
Control method | ON/OFF control or 2-PID control (with auto-tuning) | |
Control output | Relay output | SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value) |
Voltage output (for driving SSR) | Output voltage 12 VDC ±20% (PNP), max. Load current: 21 mA, with short-circuit protection circuit | |
Linear current output | 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: Approx. 10,000 | |
Auxiliary output | Number of outputs | 2 (depends on model) |
Output specifications | SPST-NO relay outputs: 250 VAC, 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value) | |
Event input | Number of inputs | 1 (depends on model) |
External contact input specifications | Contact input ON: 1 kΩ max., OFF: 100 kΩ min. | |
Non-contact input ON: Residual voltage 1.5 V max.; OFF: Leakage current 0.1 mA max. | ||
Current flow: approx. 7 mA per contact | ||
Setting method | Digital setting using front panel keys | |
Indication method | 11-segment digital displays and individual indicators Character height: PV: 8.5 mm, SV: 8.0 mm | |
Multi SP | Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations, or serial communications. *1 |
View Complete Details
Programmable Temperature Controller E5CC-T
Get Latest Price
Ratings
Power supply voltage | A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC | |
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | 7.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC | |
Sensor input | Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Analog input Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V | |
Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/THB.) | |
Control method | 2-PID control (with auto-tuning) or ON/OFF control | |
Control output | Relay output | SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value) |
Voltage output (for driving SSR) | Output voltage: 12 VDC ± 20% (PNP), max. load current: 21 mA, with short-circuit protection circuit | |
Linear current output | 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 | |
Auxiliary output | Number of outputs | 3 |
Output specifications | SPST-NO relay outputs, 250 VAC, Models with 3 outputs: 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value) | |
Event input | Number of inputs | 2 or 4 (depends on model) |
External contact input specifications | Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. | |
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. | ||
Current flow: Approx. 7 mA per contact |
View Complete Details
Programmable Temperature Controller E5CC-T
Get Latest Price
Ratings
Power supply voltage | A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC | |
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | 7.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC | |
Sensor input | Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Analog input Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V | |
Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/THB.) | |
Control method | 2-PID control (with auto-tuning) or ON/OFF control | |
Control output | Relay output | SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value) |
Voltage output (for driving SSR) | Output voltage: 12 VDC ± 20% (PNP), max. load current: 21 mA, with short-circuit protection circuit | |
Linear current output | 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 | |
Auxiliary output | Number of outputs | 3 |
Output specifications | SPST-NO relay outputs, 250 VAC, Models with 3 outputs: 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value) | |
Event input | Number of inputs | 2 or 4 (depends on model) |
External contact input specifications | Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. | |
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. | ||
Current flow: Approx. 7 mA per contact | ||
Transfer output | Number of outputs | 1 (only on models with a transfer output) |
Output specifications | Current output: 4 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 Linear voltage output: 1 to 5 VDC, load: 1 kΩ min., resolution: Approx. 10,000 | |
Setting method | Digital setting using front panel keys | |
Indication method | 11-segment digital display and individual indicators Character height: PV: 15.2 mm, SV: 7.1 mm |
View Complete Details
Programmable Temperature Controller E5AC-T
Get Latest Price
Ratings
Power supply voltage | A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC | |
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | 9.0 VA max. at 100 to 240 VAC, and 5.6 VA max. at 24 VAC or 3.4 W max. at 24 VDC | |
Sensor input | Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Analog input Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V | |
Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/THB.) | |
Control method | 2-PID control (with auto-tuning) or ON/OFF control | |
Control output | Relay output | SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA (reference value) |
Voltage output (for driving SSR) | Output voltage: 12 VDC ± 20% (PNP), max. load current: 40 mA, with short-circuit protection circuit (The maximum load current is 21 mA for models with two control outputs.) | |
Linear current output | 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 | |
Auxiliary output | Number of outputs | 4 |
Output specifications | SPST-NO. relay outputs, 250 VAC, Models with 4 outputs: 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value) | |
Event input | Number of inputs | 2, 4 or 6 (depends on model) |
External contact input specifications | Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. | |
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. | ||
Current flow: Approx. 7 mA per contact |
View Complete Details
Advanced Digital Temperature Controller (48 x 48 mm) E5CN-H
Get Latest Price
Ratings
Power supply voltage | No D in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC | |
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | 100 to 240 VAC: 8.5 VA (max.) (E5CN-HR2 at 100 VAC: 3.0 VA) 24 VAC/VDC: 5.5 VA (24 VAC)/3.5 W (24 VDC) (max.) (E5CN-HR2D at 24 VAC: 2.7 VA) | |
Sensor input | Any of the following can be selected (i.e., fully universal input). Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V | |
Input impedance | Current input: 150 Ω max., Voltage input: 1 M Ω min. (Use a 1:1 connection when connecting the ES2-HB.) | |
Control method | ON/OFF control or 2-PID control (with auto-tuning) | |
Control output | Relay output | SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA |
Voltage output (for driving SSR) | Output voltage: 12 VDC ± 15% (PNP), max. load current: 21 mA, with short-circuit protection circuit | |
Current output | 4 to 20 mA DC/0 to 20 mA DC, load: 600 Ω max., resolution: approx. 10,000 * | |
Linear voltage output | 0 to 10 VDC (load: 1 k Ω min.), Resolution: Approx. 10,000 | |
Auxiliary output | Number of outputs | 2 max. |
Output specifications | Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA |
View Complete Details
Advanced Digital Temperature Controller E5AN-H, E5EN-H
Get Latest Price
Ratings
Power supply voltage | No D in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC | |
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | 100 to 240 VAC: 12 VA 24 VAC/VDC: 8.5 VA (24 VAC)/5.5 W (24 VDC) | |
Sensor input | Any of the following can be selected. Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V | |
Input impedance | Current input: 150 Ω max., Voltage input: 1 M Ω min. (Use a 1:1 connection when connecting the ES2-HB.) | |
Control method | ON/OFF control or 2-PID control (with auto-tuning) | |
Control output | Relay output | Output Unit (Install the Output Unit (sold separately).) |
Voltage output (for driving SSR) | ||
Current output | ||
Linear voltage output | ||
Built-in SSR output | 75 to 250 VAC, 1 A (resistive load) | |
Relay output for position- proportional control | Relay output: Open and close: SPST-NO, 250 VAC, 1 A (including in-rush current), electrical life: 100,000 operations min. Potentiometer input: Must be between 100 Ω and 2.5 k Ω for maximum open position. | |
Auxiliary output | Number of outputs | 2 or 3 max. |
Output specifications | Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA | |
Event input | Number of outputs | 2 or 4 (with an E53-AKB) |
External contact input specifications | Contact input: ON: 1 k Ω max., OFF: 100 k Ω min. | |
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. | ||
Current flow: Approx. 7 mA per contact |
View Complete Details
Digital Controller E5AR
Get Latest Price
Ratings
Supply voltage (See note 1.) | 100 to 240 VAC, 50/60 Hz | 24 VAC, 50/60 Hz; 24 VDC | |
---|---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | ||
Power consumption | 22 VA max. (with maximum load) | 15 VA/10 W max. (with maximum load) | |
Sensor input (See note 2.) | Thermocouple: K, J, T, E, L, U, N, R, S, B, W Platinum resistance thermometer: Pt100 Current input: 4 to 20 mA DC, 0 to 20 mA DC (including remote SP input) Voltage input: 1 to 5 VDC, 0 to 5 VDC, 0 to 10 VDC (including remote SP input) (Input impedance: 150 Ω for current input, approx. 1 MΩ for voltage input) | ||
Control output | Voltage (pulse) output | 12 VDC, 40 mA max. with short-circuit protection circuit (E5AR-QQ[]WW-[]: 21 mA max.) | |
Current output | 0 to 20 mA DC, 4 to 20 mA DC; load: 500 Ω max. (including transfer output) (Resolution: Approx. 54,000 for 0 to 20 mA DC; Approx. 43,000 for 4 to 20 mA DC) | ||
Relay output | Position-proportional control type (open, closed) N.O., 250 VAC, 1 A (including inrush current) | ||
Auxiliary output | Relay Output N.O., 250 VAC, 1 A (resistive load) | ||
Potentiometer input | 100 Ω to 2.5 kΩ | ||
Event input | Contact | Input ON: 1 kΩ max.; OFF: 100 kΩ min. | |
No-contact | Input ON: Residual voltage of 1.5 V max.; OFF: Leakage current of 0.1 mA max. | ||
Event input | Short-circuit: Approx. 4 mA | ||
Remote SP input | Refer to the information on sensor input. | ||
Transfer output | Refer to the information on control output. | ||
Control method | 2-PID or ON/OFF control | ||
Setting method | Digital setting using front panel keys or setting using serial communications | ||
Indication method | 7-segment digital display and single-lighting indicator Character Height PV: 12.8 mm; SV: 7.7 mm; MV: 7.7 mm | ||
Other functions | Depends on model. | ||
Ambient operating temperature | -10 to 55°C (with no icing or condensation) For 3 years of assured use: -10 to 50°C (with no icing or condensation) | ||
Ambient operating humidity | 25% to 85% | ||
Storage temperature | -25 to 65°C (with no icing or condensation) |
View Complete Details
Digital Controllers E5ER
Get Latest Price
Ratings
Supply voltage (See note 1.) | 100 to 240 VAC, 50/60 Hz | 24 VAC, 50/60 Hz; 24 VDC | |
---|---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | ||
Power consumption | 17 VA max. (with maximum load) | 11 VA/7 W max. (with maximum load) | |
Sensor input (See note 2.) | Thermocouple K, J, T, E, L, U, N, R, S, B, W Platinum resistance thermometer Pt100 Current input 4 to 20 mA DC, 0 to 20 mA DC (including remote SP input) Voltage input 1 to 5 VDC, 0 to 5 VDC, 0 to 10 VDC (including remote SP input) (Input impedance 150 for current input, approx. 1 M for voltage input) | ||
Control output | Voltage (pulse) output | 12 VDC, 40 mA max. with short-circuit protection circuit | |
Current output | 0 to 20 mA DC, 4 to 20 mA DC; load 500 max. (including transfer output) (Resolution Approx. 54,000 for 0 to 20 mA DC; Approx. 43,000 for 4 to 20 mA DC) | ||
Relay output | Position-proportional control type (open, closed) N.O., 250 VAC, 1 A (including inrush current) | ||
Auxiliary output | Relay Output N.O., 250 VAC, 1 A (resistive load) Transistor Output Maximum load voltage 30 VDC; Maximum load current 50 mA; Residual voltage 1.5 V max.; Leakage current 0.4 mA max. | ||
Potentiometer input | 100 to 2.5 k | ||
Event input | Contact | Input ON 1 k max.; OFF 100 k min. | |
No-contact | Input ON Residual voltage of 1.5 V max.; OFF Leakage current of 0.1 mA max. | ||
Event input | Short-circuit Approx. 4 mA | ||
Remote SP input | Refer to the information on sensor input. | ||
Transfer output | Refer to the information on control output. | ||
Control method | 2-PID or ON/OFF control | ||
Setting method | Digital setting using front panel keys or setting using serial communications | ||
Indication method | 7-segment digital display and single-lighting indicator Character Height PV 9.5 mm; SV 7.2 mm; MV 7.2 mm | ||
Other functions | Depends on model. | ||
Ambient operating temperature | -10 to 55 DegreeC (with no icing or condensation) For 3 years of assured use -10 to 50 DegreeC (with no icing or condensation) | ||
Ambient operating humidity | 25% to 85% | ||
Storage temperature | -25 to 65 DegreeC (with no icing or condensation) |
View Complete Details
Programmable Digital Controller E5AR-T
Get Latest Price
Ratings
Supply voltage *2 | CE marking | 100 to 240 VAC, 50/60 Hz | 24 VAC, 50/60 Hz; 24 VDC |
---|---|---|---|
UL certification | 100 to 120 VAC, 50/60 Hz | ||
Operating voltage range | 85% to 110% of rated supply voltage | ||
Power consumption | 22 VA max. (with maximum load) | 15 VA/10 W max. (with maximum load) | |
Sensor input *3 | Thermocouple: K, J, T, E, L, U, N, R, S, B, W Platinum resistance thermometer: Pt100 Current input: 4 to 20 mA DC, 0 to 20 mA DC (including remote SP input) Voltage input: 1 to 5 VDC, 0 to 5 VDC, 0 to 10 VDC (including remote SP input) (Input impedance: 150 Ω for current input, approx. 1 MΩ for voltage input) | ||
Control output | Voltage (pulse) output | 12 VDC, 40 mA max. with short-circuit protection circuit (E5AR-TQQE3MW-FLK: 21 mA max.) | |
Current output | 0 to 20 mA DC, 4 to 20 mA DC; load: 500 Ω max. (including transfer output) (Resolution: Approx. 54,000 for 0 to 20 mA DC; Approx. 43,000 for 4 to 20 mA DC) | ||
Relay output | Position-proportional control type (open, closed) N.O., 250 VAC, 1 A (including inrush current) | ||
Auxiliary output | Relay Output N.O., 250 VAC, 1 A (resistive load) Transistor Output Maximum load voltage: 30 VDC; Maximum load current: 50 mA; Residual voltage: 1.5 V max.; Leakage current: 0.4 mA max. | ||
Potentiometer input | 100 Ω to 2.5 kΩ | ||
Event input | Contact | Input ON: 1 kΩ max.; OFF: 100 kΩ min. | |
No-contact | Input ON: Residual voltage of 1.5 V max.; OFF: Leakage current of 0.1 mA max. | ||
Event input | Short-circuit: Approx. 4 mA | ||
Remote SP input | Refer to the information on sensor input. | ||
Transfer output | Refer to the information on control output. | ||
Control method | 2-PID or ON/OFF control | ||
Setting method | Digital setting using front panel keys or setting using serial communications | ||
Indication method | 7-segment digital display and single-lighting indicator Character Height PV display: 12.8 mm; SV display: 7.7 mm; MV display: 7.7 mm | ||
Other functions | Depends on model. | ||
Ambient operating temperature | -10 to 55°C (with no icing or condensation) For 3 years of assured use: -10 to 50°C (with no icing or condensation) | ||
Ambient operating humidity | 25% to 85% | ||
Storage temperature | -25 to 65°C (with no icing or condensation) |
View Complete Details
Programmable Digital Controller E5ER-T
Get Latest Price
Ratings
Supply voltage *2 | CE Marking | 100 to 240 VAC, 50/60 Hz | 24 VAC, 50/60 Hz; 24 VDC |
---|---|---|---|
UL certification | 100 to 120 VAC, 50/60 Hz | ||
Operating voltage range | 85% to 110% of rated supply voltage | ||
Power consumption | 17 VA max. (with maximum load) | 11 VA/7 W max. (with maximum load) | |
Sensor input *3 | Thermocouple: K, J, T, E, L, U, N, R, S, B, W Platinum resistance thermometer: Pt100 Current input: 4 to 20 mA DC, 0 to 20 mA DC (including remote SP input) Voltage input: 1 to 5 VDC, 0 to 5 VDC, 0 to 10 VDC (including remote SP input) (Input impedance: 150 Ω for current input, approx. 1 MΩ for voltage input) | ||
Control output | Voltage (pulse) output | 12 VDC, 40 mA max. with short-circuit protection circuit | |
Current output | 0 to 20 mA DC, 4 to 20 mA DC; load: 500 Ω max. (including transfer output) (Resolution: Approx. 54,000 for 0 to 20 mA DC; Approx. 43,000 for 4 to 20 mA DC) | ||
Relay output | Position-proportional control type (open, closed) N.O., 250 VAC, 1 A (including inrush current) | ||
Auxiliary output | Relay Output N.O., 250 VAC, 1 A (resistive load) Transistor Output Maximum load voltage: 30 VDC; Maximum load current: 50 mA; Residual voltage: 1.5 V max.; Leakage current: 0.4 mA max. | ||
Potentiometer input | 100 Ω to 2.5 kΩ | ||
Event input | Contact | Input ON: 1 kΩ max.; OFF: 100 kΩ min. | |
No-contact | Input ON: Residual voltage of 1.5 V max.; OFF: Leakage current of 0.1 mA max. | ||
Event input | Short-circuit: Approx. 4 mA | ||
Remote SP input | Refer to the information on sensor input. | ||
Transfer output | Refer to the information on control output. | ||
Control method | 2-PID or ON/OFF control | ||
Setting method | Digital setting using front panel keys or setting using serial communications | ||
Indication method | 7-segment digital display and single-lighting indicator Character Height PV display: 9.5 mm; SV display: 7.2 mm; MV display: 7.2 mm | ||
Other functions | Depends on model. | ||
Ambient operating temperature | -10 to 55°C (with no icing or condensation) For 3 years of assured use: -10 to 50°C (with no icing or condensation) | ||
Ambient operating humidity | 25% to 85% | ||
Storage temperature | -25 to 65°C (with no icing or condensation) |
View Complete Details
Temperature Controllers E5CS
Get Latest Price
Ratings
Supply voltage | 100 to 240 VAC, 50/60 Hz 24 VAC, 50/60 Hz; 24 VDC | |
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | 100 to 240 VAC: 5 VA 24 VAC: 3 VA, 24 VDC: 2 W | |
Sensor input | Thermocouple: K, J, L Platinum resistance thermometer: Pt100, JPt100 Thermistor: E52-THE[][] Universal-input (thermocouple/platinum resistance thermometer): K, J, L, T, U, N, R, Pt100, JPt100 | |
Control output | Relay output | SPDT, 250 VAC, 3 A (resistive load) |
Voltage output (for driving the SSR) | 12 VDC, 21 mA (with short-circuit protection circuit) | |
Control method | ON/OFF or 2-PID (with automatic PID parameter setting function) | |
Alarm output | SPST-NO, 250 VAC, 1A (resistive load) | |
Setting method | Digital setting using front panel keys | |
Indication method | 7-segment digital display (character height: 13.5 mm) and deviation indicators | |
Other functions | Setting change prohibit (key protection) Input shift Temperature unit change (°C/°F) Direct/reverse operation Temperature range, Sensor switching (K/J/L, Pt100/JPt100) Switching is performed between a thermocouple and platinum resistance thermometer for universal-input models. Control period switching 8-mode alarm output Sensor error detection (excluding thermistor models) | |
Ambient operating temperature | -10 to 55°C (with no condensation or icing); with 3-year guarantee: -10 to 50°C | |
Ambient operating humidity | 25% to 85% | |
Storage temperature | -25 to 65°C (with no condensation or icing) |
View Complete Details
Basic-Type Digital Temperature Controller (48 x 24 mm) E5GN
Get Latest Price
Ratings
Power supply voltage | No D in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC | |
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consump- tion | E5GN Screw terminal block | 100 to 240 VAC: 5.5 VA (max.) 24 VAC/VDC: 3 VA/2 W (max.) |
E5GN-[]-C Screwless clamp terminal block | 100 to 240 VAC: 5.5 VA (max.) 24 VAC/VDC: 3 VA/2 W (max.) | |
Sensor input | Models with temperature inputs Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Voltage input: 0 to 50 mV | |
Models with analog inputs Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V | ||
Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.) | |
Control method | ON/OFF control or 2-PID control (with auto-tuning) | |
Control outputs | Relay output | SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA |
Voltage output (for driving SSR) | Output voltage: 12 VDC ± 15% (PNP), max. load current: 21 mA, with short-circuit protection circuit | |
Current output | 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 | |
Auxiliary outputs | Number of outputs | 1 or 2 max. (Depends on the model.) |
Output specifications | Relay output: SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA |
View Complete Details
Basic-Type Digital Temperature Controller (48 x 48 mm)E5CN
Get Latest Price
Ratings
Power supply voltage | No D in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC | ||
---|---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | ||
Power consumption | E5CN | 100 to 240 VAC: 7.5 VA (max.) (E5CN-R2T at 100 VAC: 3.0 VA) 24 VAC/VDC: 5 VA/3 W (max.) (E5CN-R2TD at 24 VAC: 2.7 VA) | |
E5CN-U | 100 to 240 VAC: 6 VA (max.) 24 VAC/VDC: 3 VA/2 W (max.) (models with current output: 4 VA/2 W) | ||
Sensor input | Models with temperature inputs Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Voltage input: 0 to 50 mV | ||
Models with analog inputs Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V | |||
Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.) | ||
Control method | ON/OFF control or 2-PID control (with auto-tuning) | ||
Control outputs | Relay output | E5CN | SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA |
E5CN-U | SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA | ||
Voltage output (for driving SSR) | E5CN E5CN-U | Output voltage: 12 VDC ± 15% (PNP), max. load current: 21 mA, with short-circuit protection circuit | |
Current output | E5CN | 4 to 20 mA DC/0 to 20 mA DC, load: 600 Ω max., resolution: approx. 10,000 | |
Long-life relay output | E5CN | SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 1,000,000 operations, load power supply voltage: 75 to 250 VAC (DC loads cannot be connected.), minimum applicable load: 5 V, 10 mA, leakage current: 5 mA max. (250 VAC, 60 Hz) |
View Complete Details
Basic-Type Digital Temperature Controller E5AN, E5EN
Get Latest Price
Ratings
Power supply voltage | No D in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC | |
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | 100 to 240 VAC: 10 VA 24 VAC/VDC: 5.5 VA (24 VAC)/4 W (24 VDC) | |
Sensor input | Models with temperature inputs Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Voltage input: 0 to 50 mV | |
Models with analog inputs Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V | ||
Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.) | |
Control method | ON/OFF control or 2-PID control (with auto-tuning) | |
Control output | Relay output | SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA |
Voltage output (for driving SSR) | Output voltage: 12 VDC ± 15% (PNP), max. load current: 40 mA, With short-circuit protection circuit: Max. load current of 21 mA for control output 2 | |
Current output | 4 to 20 mA DC/0 to 20 mA DC, load: 600 Ω max., resolution: approx. 10,000 | |
Long-life relay output | SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 1,000,000 operations, load power supply voltage: 75 to 250 VAC (DC loads cannot be connected.), minimum applicable load: 5 V, 10 mA, leakage current: 5 mA max. (250 VAC, 60 Hz) | |
Auxiliary output | Number of outputs | 3 |
Output specifications | Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA |
View Complete Details
Programmable Temperature Controller E5CN-HT
Get Latest Price
Ratings
Power supply voltage | No D in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC | |
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | 100 to 240 VAC: 8.5 VA (max.) (E5CN-HTR2 at 100 VAC: 3.0 VA) 24 VAC/VDC: 5.5 VA (24 VAC)/3.5 W (24 VDC) (max.) (E5CN-HTR2D at 24 VAC: 2.7 VA) | |
Sensor input | Any of the following can be selected (i.e., fully universal input). Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V | |
Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.) | |
Control method | ON/OFF control or 2-PID control (with auto-tuning) | |
Control output | Relay output | SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA |
Voltage output (for driving SSR) | Output voltage: 12 VDC ± 15% (PNP), max. load current: 21 mA, with short-circuit protection circuit | |
Current output | 4 to 20 mA DC/0 to 20 mA DC, load: 600 Ω max., resolution: approx. 10,000 * | |
Linear voltage output | 0 to 10 VDC (load: 1 kΩ min.), Resolution: Approx. 10,000 | |
Auxiliary output | Number of outputs | 2 max. |
Output specifications | Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA | |
Event input | Number of outputs | 2 |
External contact input specifications | Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. | |
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. | ||
Current flow: Approx. 7 mA per contact |
View Complete Details
Digital Temperature Controllers
Get Latest Price
E5CZ/E5CZ-U Digital Temperature ControllersRatings
Power supply voltage | 100 to 240 VAC, 50/60 Hz | 24 VAC, 50/60 Hz or 24 VDC | |
---|---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | ||
Power con- sumption | E5CZ | 7.5 VA | 5.5 VA (24 VAC)/3.5 W (24 VDC) |
E5CZ-U | 6 VA | 4.5 VA (24 VAC)/2.5 W (24 VDC) | |
Sensor input | Models with temperature inputs Thermocouple: K, J, T, E, L, U, N, R, S, or B Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor: 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Voltage input: 0 to 50 mV | ||
Models with analog inputs Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V | |||
Input impedance | Current input: 150 Ω, Voltage input: 1 MΩ (Use a 1:1 connection when connecting the ES2-HB.) | ||
Control output | Relay output | E5CZ: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA | |
E5CZ-U: SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA | |||
Voltage output (for driving SSR) | E5CZ/E5CZ-U: Output voltage: 12 VDC ±15% (PNP), max. load current: 21 mA, with short-circuit protection circuit | ||
Current output | E5CZ: 4 to 20 mA DC/0 to 20 mA DC, load: 600 Ω max., resolution: approx. 2,700 | ||
Alarm output | SPST-NO, 250 VAC, 1 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA | ||
Event input | Contact input | ON: 1 kΩ max., OFF: 100 kΩ min. | |
Non-contact input | ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. | ||
Event input | Outflow current: Approx. 7 mA per point | ||
Control method | ON/OFF control or 2-PID control (with auto-tuning) | ||
Setting method | Digital setting using front panel keys | ||
Indication method | 11-segment digital display and individual indicators (7-segments displays also possible) Character height: PV: 11 mm, SV: 6.5 mm | ||
Other functions | Manual output, heating/cooling control, transfer output (on some models), loop break alarm, multi SP, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop, protection functions, etc. | ||
Ambient operating temperature | -10 to 55°C (with no icing or condensation) | ||
Ambient operating humidity | 25% to 85% | ||
Storage temperature | -25 to 65°C (with no icing or condensation) |
View Complete Details
Temperature Controllers E5CSV
Get Latest Price
Ratings
Supply voltage | 100 to 240 VAC, 50/60 Hz 24 VAC, 50/60 Hz; 24 VDC | |
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | 100 to 240 VAC: 5 VA 24 VAC: 3 VA, 24 VDC: 2 W | |
Sensor input | Thermocouple input type: K, J, L Platinum resistance thermometer input type: Pt100, JPt100 Universal-input (thermocouple/platinum resistance thermometer) type: K, J, L, T, U, N, R, Pt100, JPt100 | |
Control output | Relay output | SPST-NO, 250 VAC, 3A (resistive load) |
Voltage output (for driving the SSR) | 12 VDC, 21 mA (with short-circuit protection circuit) | |
Control method | ON/OFF or 2-PID (with auto-tuning) | |
Alarm output | SPST-NO, 250 VAC, 1A (resistive load) | |
Setting method | Digital setting using front panel keys | |
Indication method | 7-segment digital display (character height: 13.5 mm) and deviation indicators | |
Other functions | Setting change prohibit (key protection) Input shift Temperature unit change (°C/°F) Direct/reverse operation Temperature range, Sensor switching (K/J/L, Pt100/JPt100) Switching is performed between a thermocouple and platinum resistance thermometer for universal-input models. Control period switching 8-mode alarm output Sensor error detection | |
Ambient operating temperature | -10 to 55°C (with no condensation or icing); with 3-year guarantee: -10 to 50°C | |
Ambient operating humidity | 25% to 85% | |
Storage temperature | -25 to 65°C (with no condensation or icing) |
View Complete Details
Digital Temperature Controller E5AC-800
Get Latest Price
Ratings
Power supply voltage | A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC | |
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | 7.0 VA max. at 100 to 240 VAC, and 4.2 VA max. at 24 VAC or 2.4 W max. at 24 VDC | |
Sensor input | Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Analog input Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V | |
Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/THB.) | |
Control method | ON/OFF control or 2-PID control (with auto-tuning) | |
Control output | Relay output | SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA |
Voltage output (for driving SSR) | Output voltage: 12 VDC ± 20% (PNP), max. load current: 40 mA, with short-circuit protection circuit (The maximum load current is 21 mA for models with two control outputs.) | |
Linear current output | 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 | |
Auxiliary output | Number of outputs | 1, 2, or 3 (depends on model) |
Output specifications | SPST-NO relay outputs, 250 VAC, Models with 2 outputs: 3 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V | |
Event input | Number of inputs | 2 or 4 (depends on model) |
External contact input specifications | Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. | |
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. | ||
Current flow: Approx. 7 mA per contact | ||
Potentiometer input | 100 Ω to 10 kΩ | |
Setting method | Digital setting using front panel keys | |
Indication method | 11-segment digital display and individual indicators Character height: PV: 25.0 mm, SV: 15.0 mm |
View Complete Details
Digital Temperature Controller E5CC-800
Get Latest Price
Ratings
Power supply voltage | A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC | |
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | Models with option selection of 000:5.2 VA max. at 100 to 240 VAC, and 3.1 VA max. at 24 VAC or 1.6 W max. at 24 VDC All other models: 6.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC | |
Sensor input | Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Analog input Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V | |
Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/THB.) | |
Control method | ON/OFF control or 2-PID control (with auto-tuning) | |
Control output | Relay output | E5CC-800: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA E5CC-U-800: SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA |
Voltage output (for driving SSR) | Output voltage: 12 VDC ± 20% (PNP), max. load current: 21 mA, with short-circuit protection circuit | |
Linear current output | 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 | |
Auxiliary output | Number of outputs | 2 |
Output specifications | SPST-NO relay outputs, 250 VAC, Models with 2 outputs: 3 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V | |
Event input | Number of inputs | 2 or 4 (depends on model) |
External contact input specifications | Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. | |
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. | ||
Current flow: Approx. 7 mA per contact | ||
Setting method | Digital setting using front panel keys |
View Complete Details
Digital Temperature Controller E5EC-800
Get Latest Price
Ratings
Power supply voltage | A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC | |
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | 6.6 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC | |
Sensor input | Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Analog input Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V | |
Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/THB.) | |
Control method | ON/OFF control or 2-PID control (with auto-tuning) | |
Control output | Relay output | SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA |
Voltage output (for driving SSR) | Output voltage: 12 VDC ± 20% (PNP), max. load current: 40 mA, with short-circuit protection circuit (The maximum load current is 21 mA for models with two control outputs.) | |
Linear current output | 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 | |
Auxiliary output | Number of outputs | 1, 2, or 3 (depends on model) |
Output specifications | SPST-NO relay outputs, 250 VAC, Models with 2 outputs: 3 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V | |
Event input | Number of inputs | 2 or 4 (depends on model) |
External contact input specifications | Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. | |
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. | ||
Current flow: Approx. 7 mA per contact | ||
Potentiometer input | 100 Ω to 10 kΩ | |
Setting method | Digital setting using front panel keys | |
Indication method | 11-segment digital display and individual indicators Character height: PV: 18.0 mm, SV: 11.0 mm | |
Multi SP | Up to eight set points (SP0 to SP7) can be saved and selected using event inputs, key operations, or serial communications. | |
Bank switching | None | |
Other functions | Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, self tuning, PV input shift, run/stop, protection functions, temperature status display, moving average of input value, FB moving average |
View Complete Details
Programmable Temperature Controller E5AN-HT, E5EN-HT
Get Latest Price
Ratings
Power supply voltage | No D in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC | |
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | 100 to 240 VAC: 12 VA 24 VAC/VDC: 8.5 VA (24 VAC)/5.5 W (24 VDC) | |
Sensor input | Any of the following can be selected. Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V | |
Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB.) | |
Control method | ON/OFF control or 2-PID control (with auto-tuning) | |
Control output | Relay output | Output Unit (Install the Output Unit (sold separately).) |
Voltage output (for driving SSR) | ||
Current output | ||
Linear voltage output | ||
Relay output for position-proportional control | Relay output: Open and close: SPST-NO, 250 VAC, 1 A (including in-rush current), electrical life: 100,000 operations min. Potentiometer input: Must be between 100 Ω and 2.5 kΩ for maximum open position. | |
Auxiliary output | Number of outputs | 2 or 3 max. |
Output specifications | Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA | |
Event input | Number of outputs | 2 or 4 (with an E53-AKB) |
External contact input specifications | Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. | |
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. | ||
Current flow: Approx. 7 mA per contact | ||
Logic operations | Number of operations | 8 max. |
Operations | Logic operation: Any of the following four patterns can be selected. The input status may be inverted. (A and B) or (C and D), (A or C) and (B or D), A or B or C or D, A and B and C and D (A, B, C, and D are four inputs.) Delay: ON delay or OFF delay for the results of the logic operation given above. Setting time: 0 to 9999 s or 0 to 9999 min Output inversion: Possible | |
Output | One work bit per operation | |
Work bit assignment | Any of The following can be assigned to up to eight work bits (logic operation results): operation commands (assigned to event inputs)* , auxiliary outputs, or control outputs. * Application is possible with models that do not have event inputs by using an internal assignment. |
View Complete Details
Temperature Controller E5C2
Get Latest Price
Ratings
Supply voltage | 100 to 240 VAC 50/60 Hz |
---|---|
Operating voltage range | 90% to 110% of rated supply voltage |
Power consumption | Approx. 3.6 VA |
Input | Thermocouple (with sensor burnout detection circuit), platinum resistance thermometer, or thermistor with replaceable element |
Control mode | ON/OFF or proportional control |
Setting method | Analog setting |
Indication method | No indication |
Control output | Relay output: SPDT, 3 A at 250 VAC, resistive load (switching capacity: 330 VA) |
Ambient operating temperature | - 10°C to 55°C (with no icing or condensation) |
Ambient operating humidity | 45% to 85% |
Note: Do not use an inverter output as the power supply. (Refer to Safety Precautions for All Temperature Controllers.)
Characteristics
Setting accuracy | ±2% FS max. |
---|---|
Hysteresis | Approx. 0.5% FS (fixed) |
Proportional band | 3% FS (fixed) |
Control period | Approx. 20 s |
Reset range | 5 ±1% FS min. *1 |
Insulation resistance | 20 MΩ min. (at 500 VDC) |
Dielectric strength | 2,000 VAC, 50/60 Hz for 1 min between charged terminals and uncharged metallic parts |
Vibration resistance | Malfunction: 10 to 55 Hz, 0.15-mm single amplitude for 10 min each in X, Y, and Z directions Destruction: 16.7 Hz, 2-mm double amplitude for 2 hrs each in X, Y, and Z directions |
Shock resistance | Malfunction: 147 m/s2, 3 times each in 6 directions Destruction: 294 m/s2, 3 times each in 6 directions |
Life expectancy | Electrical: 100,000 operations min. (3 A at 110 VAC, resistive load) |
Weight | Approx. 100 g (with flush-mounting adapter) |
Degree of protection | Front panel: IEC standard IP40 *2 Terminals: IEC standard IP00 |
Applicable Socket | P2CF-08 (order separately), P3G-08 (order separately) |
Applicable Protective Cover | Y92A-48B (order separately) |
View Complete Details
Electronic Thermostat E5L
Get Latest Price
Ratings
Model | E5L-A[] | E5L-C[] |
---|---|---|
Power supply voltage | 100 to 240 VAC, 50/60 Hz | |
Operating voltage range | 85% to 110% of the rated supply voltage | |
Power consumption | Approx. 3 VA | |
Inputs | Element-interchangeable thermistor | |
Control method | ON/OFF control | |
Control output | SPDT contacts, 250 VAC, 10 A, cosΦ = 1 (resistive load) | SPST-NO contacts, 250 VAC, 10 A, cosΦ = 1 (resistive load) |
Setting method | Analog setting | Digital settings using keys on front panel |
Indication method | No display | LCD digital display (character height: 12 mm) |
Other functions | Setting protection (key protection) Input shift Direct/reverse operation | |
Ambient temperature | -10 to 55°C (with no icing or condensation) | |
Ambient humidity | 25% to 85% | |
Storage temperature | -25°C to 65°C (with no icing or condensation) |
Note: Do not use the output from an Inverter as the power supply.
Characteristics
Model | E5L-A[] | E5L-C[] |
---|---|---|
Indication accuracy | --- | ±(1°C 1 digit) max.* |
Setting accuracy | --- | ±(1°C 1 digit) max.* |
Hysteresis | -30 to 20°C models: Approx. 0.5 to 2.5°C (variable) 0 to 50°C models: Approx. 0.5 to 4°C (variable) 0 to 100°C models: Approx. 0.5 to 4°C (variable) 100 to 200°C models: Approx. 0.7 to 4°C (variable) | 1 to 9°C (in increments of 1°C) |
Repeat accuracy | 1% FS max. | --- |
Minimum scale (standard scale) | -30 to 20°C models and 0 to 50°C models: 5°C 0 to 100°C models and 100 to 200°C models: 10°C | --- |
Influence of temperature | --- | ±((1% of PV or 2°C, whichever is greater) 1 digit) max. |
Influence of voltage | --- | |
Sampling period | --- | 2 s |
Insulation resistance | 100 MΩ max. (at 500 VDC) | |
Dielectric strength | 2,300 VAC, 50/60 Hz for 1 min (between charged terminals and uncharged metallic parts, between power supply terminals and input terminals, between power supply terminals and output terminals, and between input terminals and output terminals) |
View Complete Details
Temperature Controllers E5CSL / E5CWL / E5EWL
Get Latest Price
Ratings
Power supply voltage | 100 to 240 VAC, 50/60 Hz | |
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | 3.5 VA | |
Sensor input | Models with thermocouple inputs Thermocouple: K, J, T, R, or S | |
Models with platinum resistance thermometer inputs Platinum resistance thermometer: Pt100 | ||
Control output | Relay output | SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum load: 5 V, 10 mA |
Voltage output (for driving SSR) | Output voltage: 12 VDC 25%/-15% (PNP), max. load current: 21 mA, with short- circuit protection circuit | |
Alarm output * | SPST-NO, 250 VAC, 1 A (resistive load), electrical life: 100,000 operations, minimum load: 5 V, 10 mA | |
Control method | ON/OFF control or 2-PID control (with auto-tuning) | |
Setting method | Digital setting using front panel keys | |
Indication method | 7-segment digital display and individual indicators Character height: E5CSL: 21.7 mm, E5CWL: 16.2 mm (PV), E5EWL: 20 mm (PV) | |
Other functions | Temperature input shift, run/stop, protection functions, etc. | |
Ambient operating temperature | -10 to 55°C (with no icing or condensation) | |
Ambient operating humidity | 25% to 85% | |
Storage temperature | -25 to 65°C (with no icing or condensation) |
View Complete Details
Modular Temperature Controller EJ1
Get Latest Price
Basic Unit/EJ1N-TCRatings
Type | EJ1N-TC4 | EJ1N-TC2 | |
---|---|---|---|
Power supply voltage | 24 VDC | ||
Operating voltage range | 85% to 110% of rated voltage | ||
Power consumption | 5 W max. (at maximum load) | 4 W max. (at maximum load) | |
Input * | Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII ES1B Infrared Thermosensor: 10 to 70°C, 60 to 120°C, 115 to 165°C, 140 to 260°C Analog input: 4 to 20 mA, 0 to 20 mA, 1 to 5 V, 0 to 5 V, 0 to 10 V Platinum resistance thermometer: Pt100, JPt100 | ||
Input impedance | Current input: 150 Ω max., voltage input: 1 MΩ min. | ||
Control outputs | Voltage output | Output voltage: 12 VDC ±15%, max. load current: 21 mA (PNP models with short-circuit protection circuit) | |
Transistor output | --- | Max. operating voltage: 30 V, max. load current: 100 mA | |
Current output | --- | Current output range: 4 to 20 mA or 0 to 20 mA DC Load: 500 Ω max. (including transfer output) (Resolution: Approx. 2,800 for 4 to 20 mA DC, approx. 3,500 for 0 to 20 mA DC) | |
Event inputs | Input points | --- | 2 |
Contact input | --- | ON: 1 kΩ max., OFF: 100 kΩ min. | |
Non-contact input | --- | ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. | |
Event inputs | --- | Outflow current: Approx. 4 mA per point | |
Number of input and control points | Input points: 4, Control points: 4 | Input points: 2, Control points: 2 | |
Setting method | Via communications | ||
Control method | ON/OFF control or 2-PID (with autotuning, self-tuning) [V1.2] | ||
Other functions | Two-point input shift, digital input filter, remote SP, SP ramp, manual manipulated variable, manipulated variable limiter, interference overshoot adjustment, loop burnout alarm, RUN/ STOP, banks, I/O allocations, etc. | ||
Ambient temperature range | Operating: -10°C to 55°C, Storage: -25°C to 65°C (with no icing or condensation) | ||
Ambient humidity range | Operating: 25% to 85% (with no condensation) |
View Complete Details
Modular Temperature Controller E5ZN
Get Latest Price
Ratings
Power supply voltage | 24 VDC | ||
---|---|---|---|
Allowable voltage range | 85% to 110% of the rated power supply voltage | ||
Power consumption | Approx. 3 W | ||
Sensor input | Thermocouple: K, J, T, E, L, U, N, R, S, B Infrared temperature sensor (ES1B series): 10 to 70℃, 60 to 120℃, 115 to 165℃, 140 to 260℃ Voltage input: 0 to 50 Mv | ||
Platinum resistance thermometer: Pt100, JPt100 | |||
Control output | Voltage output (for driving SSR) | Output voltage: 12 VDC ±15% (PNP); Maximum load current: 21 mA; Equipped with short-circuit protection circuit | |
Transistor output | Maximum operational voltage: 30 VDC; Maximum load current: 100 mA; Residual voltage: 1.5 V max.; Leakage current: 0.4 mA max. | ||
Current output | Current output range: 4 to 20/0 to 20 mA DC; Load: 350 Ω max. (See note 2.) | ||
Auxiliary output | Transistor output | Sourcing | Maximum operating voltage: 30 VDC; Maximum load current: 50 mA; Residual voltage: 1.5 V max.; Leakage current: 0.4 mA max. |
Sinking | |||
Linear voltage output | Voltage output range: 1 to 5/0 to 5 VDC; Load: 10 kΩ min. | ||
Event input | Contact output | ON: 1 kΩ max., OFF: 100 kΩ min. Discharge current: Approx. 7 mA | |
Non-contact output | ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. Discharge current: Approx. 7 mA | ||
Number of input and control points | Input points: 2, Control points: 2 | ||
Setting method | Via communications or using the Setting Display Unit (E5ZN-SDL) | ||
Control method | 2-PID or ON/OFF control | ||
Other functions | Heater burnout detection function, transfer output function Multi-SP and RUN/STOP switching using event input | ||
Ambient operating temperature | -10 to 55℃ (with no icing or condensation) For 3 years of assured use: -10 to 50℃ | ||
Ambient operating humidity | 25% to 85% | ||
Storage temperature | -25 to 65℃ (with no icing or condensation) |
View Complete Details
Device Net Communications Unit E5ZN-DRT
Get Latest Price
Ratings
Power supply voltage | DeviceNet | 24 VDC (for internal circuits) |
---|---|---|
External input power supply | 24 VDC (for RS-485 communications circuits and Temperature Controllers) | |
Allowable voltage range | DeviceNet | 11 to 25 VDC |
External input power supply | 20.4 to 26.4 VDC | |
Power consumption (See note 2.) | DeviceNet | Approx. 1.1 W (for a current of 45 mA at 24 VDC) |
External input power supply | Approx. 0.5 W (for a current of 20 mA at 24 VDC) | |
Connectable Temperature Controllers | E5ZN Series | |
Maximum number of connectable Temperature Controllers | 16 | |
Ambient operating temperature | -10 to 55°C (with no icing or condensation) | |
Ambient operating humidity | 25% to 85% | |
Ambient storage temperature | -25 to 65°C (with no icing or condensation) |
View Complete Details
CJ Series Temperature Control Unit CJ1W-TC
Get Latest Price
General Specifications
Item | Specification | |||
---|---|---|---|---|
Unit classification | CJ-series Special I/O Unit | |||
Compatible Racks | CJ-series CPU Rack or CJ-series Expansion Rack | |||
Max. number of Units | 10 Units/Rack max. (CPU Rack or Expansion Rack) | |||
CPU Unit data areas for data storage/exchange | Special I/O Unit Area (960 words) CIO 2000 to CIO 2959 | 20 words/Unit for constant data exchange (6 output words and 14 input words) | CPU Unit to Temperature Control Unit | Set point (SP) Operating commands RUN/STOP control Start/Stop AT Write commands Heater burnout set value |
Temperature Control Unit to CPU Unit | Process value (PV) Set point (SP) Status Heater current monitor | |||
DM words allocated to Special I/O Units (9,600 words) D20000 to D29599 | 10 words/Unit transferred when power is turned ON or Unit is restarted | CPU Unit to Temperature Control Unit | Alarm mode Alarm hysteresis | |
90 words/Unit for regular data exchange | Two-way transfer between CPU Unit and Temperature Control Unit | Alarm value Input compensation value Control period Hysteresis Proportional band Integral time Derivative time Output monitor | ||
Insulation resistance | 20 M Ω min. (at 500 VDC) between the following points: All output and NC terminals and external AC terminals (Power Supply Unit) All input terminals and external AC terminals (Power Supply Unit) All input terminals and all output terminals All external DC terminals (inputs, outputs, and NC) and the FG plate Between input terminals (sensor and CT inputs) I/O terminals and NC terminals | |||
Dielectric strength | 2,000 VAC 50/60 Hz for 1 min., detected current: 1 mA The output terminals/NC terminals and external AC terminals (Power Supply Unit) 1,000 VAC 50/60 Hz for 1 min., detected current: 1 mA Input terminals and external AC terminals (Power Supply Unit) Input terminals and output terminals External DC terminals (inputs, outputs, and NC) and the FG plate 500 VAC 50/60 Hz for 1 min., detected current: 1 mA Between input terminals (sensor and CT inputs) I/O terminals and NC terminals |
View Complete Details
CX-Thermo Support Software EST2-2C-MV4
Get Latest Price
mpatible devices | Temperature Controllers | E5GN * (available from Sep. 2009) E5CN (available from April 2004) E5EN,E5AN(available from February 2005), E5CN-H, E5EN-H, E5AN-H E5CN-HT, E5EN-HT, E5AN-HT E5ER, E5AR E5ER-T, E5AR-T E5CC, E5EC, E5AC, E5DC E5CC-T, E5EC-T, E5AC-T E5ZN EJ1N-TC4, EJ1N-TC2, EJ1N-HFU EJ1G-TC4, EJ1G-TC2, EJ1G-HFU G3ZA (only when connected to EJ1N-TC4, EJ1N-TC2, EJ1G-TC4, EJ1G-TC2) G3PW (only when connected to EJ1N-TC4, EJ1N-TC2) Note: Models with DeviceNet communications are not supported. |
---|---|---|
Personal computer system requirements | OS | OS: Microsoft Windows XP (Service Pack 3 or higher), Vista, 7 or 8 CPU: A processor recommended by Microsoft Memory: A memory recommended by Microsoft |
CPU | 300 MHz min. | |
Memory | 128 MB min. | |
Harddisk | 300 MB min. available space | |
CD-ROM | One CD-ROM drive min. | |
Monitor | XGA (1024 × 768), High Color 16 bit min. | |
Communications ports | RS-232C port, or USB port, 1 port min. | |
Connection method | An E58-CIFQ1 USB-Serial Conversion Cable is required to connect a computer to the setup tool port the E5[]N, E5[]N-H, E5[]N-HT, or EJ1. An E58-CIFQ2 USB-Serial Conversion Cable is required to connect a computer to the setup tool port the E5CC, E5EC, E5AC, E5DC, E5CC-T, E5EC-T, or E5AC-T A K3SC Interface Converter is used to connect a computer to models with RS- 422/RS-485 communications. An E58-CIFIR USB-Infrared Conversion Cable is required to wirelessly connect a computer to models with infrared communications (E5EN-H/EN-HT or E5AN-H/ AN-HT). |
View Complete Details
ThermoTools Support Software ESTT
Get Latest Price
Basic functions | Offline | Creating, changing, and saving parameters (Some parameters must be set on the Temperature Controller. Use the switches and keys on the Temperature Controller to set those parameters.) |
---|---|---|
Online | Uploading and downloading parameters. Editing parameters during operation, data log viewer, and simple data logging. | |
Compatible models | Temperature Controllers | E5[]R, E5[]K, E5ZN, and E5ZE Series (models with communications) |
Digital Panel Meters | K3N[]and K3GN Series (models with communications) | |
Personal computer system requirements | CPU | Pentium, 133 MHz or higher |
OS | Windows 2000 | |
Memory | 64 MB min. | |
Hard disk | 650 MB min. available space | |
CD-ROM | One CD-ROM drive | |
Communications ports | RS-232C ports COM1 to COM4 (A USB port can be used if the OMRON K3SC Communications Adapter is used.) | |
Monitor | SVGA (800 × 600). Recommended: XGA (1024 × 768), high color (16 bits) min. |
View Complete Details
Temperature Sensor E52-THE5A / 6D / 6F
Get Latest Price
Temperature Ranges
Temperature range | Color code | Nominal resistance | Thermistor constant | Lead wire |
---|---|---|---|---|
-50°C to 50°C | Blue | 6 kΩ (0°C) | 3390K | A pair of 0.12 dia. 7 Fluororesin-insulated stranded wires with 0.86 outer dia. each |
0°C to 100°C | Black | 6 kΩ (0°C) | 3390K | |
50°C to 150°C | Red | 30 kΩ (0°C) | 3450K | |
100°C to 200°C | Yellow | 0.55 kΩ (200°C) | 4300K | |
150°C to 300°C | Green | 4 kΩ (200°C) | 5133K | Flat glass-wool-shielded lead cable with 0.12 dia. 10 conductors and external dimensions of 2.5 × 1.55 |
Specifications
Item | E52-THE[][] |
---|---|
Coupling method | Element interchangeable thermistor |
Class | JIS class 1 |
Protective tubing material | SUS304 |
Time constant | 8 to 15 s in still water |
Dissipation factor | 2.4 to 2.8 mW/°C in still air |
Lead wire heat resistive temperature | 180°C |
View Complete Details
Infrared Thermosensor ES1B
Get Latest Price
Item | ES1B | |
---|---|---|
Power supply voltage | 12/24 VDC | |
Operating voltage range | 90% to 110% of the power supply voltage | |
Current consumption | 20 mA max. | |
Measuring temperature range | 10 to 70°C, 60 to 120°C, 115 to 165°C, 140 to 260°C | |
Accuracy *1 | ±5°C *2 | ±2% PV or ±2°C, whichever is larger |
±10°C *2 | ±4% PV or ±4°C, whichever is larger | |
±30°C *2 | ±6% PV or ±6°C, whichever is larger | |
±40°C *2 | ±8% PV or ±8°C, whichever is larger | |
Reproducibility | ±1% PV or ±1°C, whichever is larger | |
Temperature drift | 0.4°C/°C max. | |
Sensing distance vs. sensing diameter | 1:1 typ. | |
Measurement wavelength | 6.5 to 14.0 μm | |
Receiver element | Thermopile | |
Response speed | Approximately 300 ms at response rate of 63% | |
Output impedance | 1 to 4 kΩ | |
Operating temperature | -25°C to 70°C (with no icing or condensation) | |
Allowable ambient humidity | 35% to 85% | |
Vibration resistance (destruction) | 98 m/s2 for 2 hours each in X, Y, and Z directions at 10 to 55 Hz | |
Shock resistance (destruction) | 300 m/s2 for 3 times each in X, Y, and Z directions | |
Casing material | ABS resin | |
Degree of protection | IP65 | |
Applicable safety standards | CE Marking | |
Weight | Approx. 120 g | |
Cable | Compensating conductor: 3 m | |
PVC-covered cable with a shield wire resisting 70°C |
View Complete Details
Infrared Thermo Sensors ES1C
Get Latest Price
Model | ES1C |
---|---|
Power supply voltage | 12 to 24 VDC |
Operating voltage range | 90% to 110% of rated voltage |
Current consumption | 70 mA max. |
Measuring temperature range | 0 to 400°C |
Measurement accuracy | 0 to 200°C: ±2°C, 201 to 400°C: ±1% PV (emissivity: 0.95) |
Response time | 100 ms/90% |
Reproducibility | ±1% of reading value |
Measurement wavelength | 8 to 14 μm |
Light-receiving element | Thermopile |
Emissivity | 0.95 fixed |
Current output | 4 to 20 mA DC, Load: 250 Ω max. |
Ambient temperature range | Operating: 0 to 70°C, Storage: -20 to 70°C (with no icing or condensation) |
Ambient humidity range | Operating and storage: 35% to 85% |
Vibration resistance (destruction) | 1.5-mm amplitude at 10 to 55 Hz for 2 hours each in the X, Y, and Z directions |
Weight | 180 g |
Degree of protection | Equivalent to IP67 |
Applicable safety standards | CE Marking |