Model Name | ACS5000 Medium Voltage Drives |
Power Range | 1.5 MW to 36 MW |
Inverter type | Voltage Source Inverter Multilevel-Fuseless;IGCTs,w/o parallel/series connected device |
Supported Motors | Induction, synchronous and permanent magnet motors |
Input | Medium voltage input transformer for 36-pulse diode rectifier |
Voltage variation | +/-20% of nominal voltage (optionally up to +40%), down to-30% safe operation with derated output |
Input power factor | Fundamental Greater Than 0.96; Total Greater Than 0.95 |
Model Name | ACS5000 Medium Voltage Drives |
Power Range | 1.5 MW to 36 MW |
Inverter type | Voltage Source Inverter Multilevel-Fuseless;IGCTs,w/o parallel/series connected device |
Supported Motors | Induction, synchronous and permanent magnet motors |
Input | Medium voltage input transformer for 36-pulse diode rectifier |
Voltage variation | +/-20% of nominal voltage (optionally up to +40%), down to-30% safe operation with derated output |
Input power factor | Fundamental Greater Than 0.96; Total Greater Than 0.95 |
Output voltage | Standard 6.0-6.9 kV; Optional 4.16 kV |
Output frequency | 0 to +/-75 Hz, up to +/-250 Hz optional (higher on request) |
Efficiency of converter | Typically Greater Than 98.5% (incl. auxiliaries) |
UPS (Uninterruptible Power Supply) | UPS can be used for control power supply,110-240 VAC 1ph or 110/220 VDC. |
Auxiliary voltage | Common 380-480 VAC, 3-phase, 50 Hz/60 Hz, (up to 690 VAC for water cooled drives) |
Standard protection functions | +/-20% of nominal voltage (upto +40% optional), down to -30% safe operation,derated output |
Description | |
Ambient temperature | +1° C to 40° C (higher with derating)/34° F to 104° F (higher with derating) |
Enclosure classes | IP 21 air cooled; IP 32 water cooled(standard)/ up to IP 42 air cooled; up to IP 54 water cooled(optional) |
Standard protection functions | Overload, stall protection |
Compliant Standards | All common standards including EN, IEC, CE |
Options/Add-ons | |
Fieldbus Options | All common field buses including Profibus, Modbus, Allen-Bradley DeviceNet, Ethernet, ABB Advant Fieldbus AF100 (others on request) |
I/O Options | |
Motor supervision I/Os | Fault/alarm: overtemperature, a vibration of bearings |
PT 100: winding and bearing temperatures | |
Transformer supervision I/Os: | Fault/alarm: overtemperature, Buchholz |
PT 100: winding temperatures | |
Hardwired signals for remote drive control | References: start/stop, speed/torque, etc. |
Status feedback signals: ready/running | |
Analog signals: current/voltage/power, etc. | |
Cooling Options | Redundant cooling fan (air-cooled ACS 5000) and pump (water-cooled ACS 5000) for enhanced reliability |
Synchronous bypass functionality | for starting of up to six different motors |
Software Options | ABB DriveMonitorTM for remote monitoring and diagnostics |
Integrated transformer, input voltage range | −−6.0–6.9 kV, 50 Hz/60 Hz |
−− 10.0–11.0 kV, 50 Hz/60 Hz | |
−−11.0–13.8 kV, 50 Hz/60 Hz on demand |